EasyManua.ls Logo

Eaton VCP-W - Safe Practices for VCP-W Circuit Breakers; Recommendations for Safe Operation

Eaton VCP-W
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
I.L. 3778A20B
Page 10
Effective 11/97
Figure 6 Control Scheme - Power Trip
Control Switch Box with 50 ft. # 14-3 Cable
and 3 Prong Male Twist Lock Connector
Ground and Test Device has 3 Hole Female Socket
KT
PS
WHITE
CLOSE
OPEN
W
1
TD
X
Z
R
24
TD
M
SR
Y
ST
GREEN
OR
RED
TD
Y
LS1
b
LS2
b
Y
Y
a
a
CS = Control Switch:
Vertical : No Circuit (Spring Return Position)
CW : Close
CCW : Trip
Y = Anti Pump Relay
M = Charging Motor
LS = Limit Switch (Shown - Spring Discharged)
ST = Shunt Trip Coil
TD = Time Delay Relay : Seals in to Complete Charging & Closing,
20 Seconds Delay on Dropout, Blocks Tripping for 20 Seconds
After Closing
a = Auxiliary Switch Contact
b = Auxiliary Switch Contact
SR = Spring Release coil
KT = Key Interlock Contact
R = Bridge Rectifier
PS = Position Switch (Prevents Charging Between “Test” and
“Connected” Positions)

Other manuals for Eaton VCP-W