IB131009EN
W-VAC Breaker Element
W
-
VAC 3150A Breaker with Carriage
A
ssembl
y
for Single Tier Switchgear
W-VAC Breaker with Carriage
A
ssembl
y
for Single Tier Switchgea
r
W-VAC Breaker with Cradle
A
ssembl
y
for Double Tier Switchgea
r


Table of Contents

Questions and Answers

  • N
    nathannelsonAug 27, 2025
    Why do Eaton Circuit breakers undesirably closes?
    • A
      Anne BowenAug 27, 2025
      If your Eaton Circuit breaker undesirably closes, it could be due to: * A short in the close circuit (CS/C getting shorted). To resolve this, check for a short in the close circuit. * The close release latch failing to reset. In this case, inspect the close release latch.
  • D
    Debra BonillaSep 2, 2025
    What to do if Eaton W-VAC undesirably trips?
    • C
      Catherine NovakSep 2, 2025
      If your Eaton Circuit breaker undesirably trips, the issue might stem from: * The control power (SD/T switch) remaining made; in this case, check the control power. * The trip coil clapper not resetting; inspect the trip coil clapper. * Poor engagement or worn surfaces on the trip bar or trip latch; inspect the trip bar or trip latch. * Loss of torque in the trip bar reset spring; inspect the trip bar reset spring.
  • J
    James ChenNov 10, 2025
    What to do if Eaton Circuit breakers fails to trip?
    • P
      Pedro DavisNov 10, 2025
      If your Eaton Circuit breaker fails to trip, it might be due to several reasons: * The control power fuse may be blown, or the switch is off; in this case, check the control power. * There might be an issue with the secondary disconnect; examine the secondary disconnect. * The auxiliary switch (a contact) may not be making good contact, or it could be poor or burned; inspect the auxiliary switch. * The trip coil could be burned or open; check the trip coil. * Terminals and connections may be poor, burned, or open; inspect the terminals and connections. * The trip clapper might be jammed; inspect the trip clapper. * The trip bar or trip latch could be jammed; check the trip bar and trip latch. * The pole shaft may be jammed; inspect the pole shaft. * The operating rod ass...
  • S
    Sonya WrightNov 17, 2025
    How to troubleshoot Eaton W-VAC Circuit breakers that fails to close?
    • Z
      zgregoryNov 18, 2025
      If your Eaton Circuit breaker fails to close, here are several potential causes: * **Control Power:** A blown fuse or a switched-off control power can prevent closing. Check the control power. * **Secondary Disconnects:** Faulty secondary disconnects can be the issue. Inspect the secondary disconnects. * **Anti-Pump Relay:** Problems with the anti-pump relay, such as an open or burned N.C. contact, or the relay picking up, can cause this. Examine the anti-pump relay. * **Close Coil:** An open or burned close coil will prevent closing. Check the close coil. * **Latch Check Switch:** An open contact, a bad switch, or a trip bar that isn't reset can be the cause. Inspect the latch check switch. * **Auxiliary Switch:** An open or burned 'b' contact on the auxiliary switch can be t...

Eaton W-VAC Series Specifications

General IconGeneral
Frequency50/60 Hz
Interrupting Rating25 kA, 31.5 kA, 40 kA, 50 kA
ApplicationIndustrial, Commercial
Poles3
Breaking Capacity25 kA, 31.5 kA, 40 kA, 50 kA