The data collected on the J2K with Multi Media Card will open in a spreadsheet with the recorded on
calculated values displayed in the following format.
Column Description Range/Comment/Example
A Date DD.MM.YYYY 13:02:2006 (February 13, 2006)
B Time HH:MM:SS 09:36:54 (9:36:54 AM)
C O2 in vol.% 0.0 – 21.0
D CO in ppm 0 - 4000
E NO in ppm 0 – 4000 Standard, 0.0 300.0 Low NOx
F NO2 in ppm 0 – 500 Standard, 0.0-50.0 Low NOx
G SO2 in ppm 0 – 5000 (0 if SO2 sensor not installed)
H CO w/ O2 correction applied 0.0-20.0 %
I NO w/ O2 correction applied 0.0-20.0 %
J NO2 w/ O2 correction applied 0.0-20.0 %
K NOX w/ O2 correction applied 0.0-20.0 %
L SO2 w/ O2 correction applied 0.0-20.0 % (0 if SO2 sensor not installed)
M T.Gas in °C or °F Exhaust Gas temperature w/ probe
N T.Air in °C or °F Ambient Air temperature at instrument
O Draft in “ H2O 0.0 – 40.0 inches water gage
P CO2 in vol.% 0.0 25.0
Q Efficiency in % 0.0 – 100.0
R Losses in % 0.0 – 100.0
S Excess air (Lambda) 1.00 = 0.00% excess air, 1.20 = 20% excess air
T Dew point in °C or °F
U Poisoning index
V O2 (gas channel check) in vol.% 0.0 – 21.0
W CO (gas channel check) in ppm related to 0,0 vol.% O2
X CO (gas channel check) in ppm Measured value
Y O2 (check if O2 mixed) in vol.% 0.0 – 21.0
Z T. Boiler 0 - 999
AA T. Sensor (internal sensor temp) 0 – 99 F
AB O2 Correction 0.0 – 21.0 (programmed by user)
AC Unit of measure 0=ppm; 1=mg/m3; 2=mg/kWh; 3=mg/MJ
AD O2 Correction N= O2 correction value.
AE Fuel type number Refer to instrument fuel choices
AF Fuel type text Refer to instrument fuel choices
AG Soot Test # 1 value 0.0 – 9.9
AH Soot Test # 2 value 0.0 – 9.9
AI Soot Test # 3 value 0.0 – 9.9
AJ Oil trace 0=no; 1=yes;