Troubleshooting
Issues Configuring Firmware
cmd
not found after entering a zb
command.
Backspace was used while typing
the zb command.
zb
using backspace.
The channel was not set to the
value I entered.
below 11 or above 26.
zb
Recommended channels are 15, 20,
25, and 26.
Backspace was used while typing
the zb command.
zb
using backspace.
The PAN was not set to the value I
entered.
specified in hexadecimal.
zb –p
ensuring you preface the PAN value
with 0x, such as 0x201.
Backspace was used while typing
the zb command.
zb
using backspace.
The ShortAdd shows the default
value of 0xFFFF.
EcoConnect are not configured
with the same channel.
value into the
EcoInsight/EcoSource.
The EcoInsight/ EcoSource and
EcoConnect are not configured
with the same PAN.
into the EcoInsight/EcoSource.
The EcoInsight/ EcoSource cannot
communicate with the EcoConnect
due to interference.
EcoInsight/EcoSource and
EcoConnect to use a different
channel. Recommended channels
are 15, 20, 25, and 26.
code, the EcoSource LED does not
blink a "Red, Red, Green"
sequence.
EcoInsight: After entering the join
code, the EcoInsight does not
display the two horizontal bars
appear above "Room Temp".
The join code was not entered
properly.
into the EcoInsight/EcoSource.