© 2013 UTC Fire & Security. All rights reserved.  1 / 2  P/N 3101062 • REV 02 • REB 13FEB13 
 
MPSR Series Outdoor Manual Station 
Installation Sheet 
Product description 
This installation sheet covers the following model numbers. 
 
  Models 
  MPSR1-SHTW-GE  MPSR1-S45W-GE 
MPSR1-DHTW-GE  MPSR1-D45W-GE 
  MPSR2-SHTW-GE  MPSR2-D45W-GE 
MPSR2-S45W-GE  MPSR2-SHTW-GE-NYW 
MPSR2-DHTW-GE  MPSR2-S45W-GE-NYW 
 
The manual pull station is a high quality non-toxic die-cast 
manual pull station for use outdoors. All components are pre-
painted or have plated surfaces to inhibit corrosion. The 
manual pull station has a 10 A snap action switch and gold 
contacts and can be used with or without a break glass rod 
with replacement requiring no special tools. Each manual 
station can be reset and locked using the standard key or hex 
key provided. 
Installation instructions 
Note: The manual stations are supplied with the glass rods 
removed. It is recommended that the station be activated and 
tested prior to installation of the glass rod. 
To install the MPSR series manual stations: 
1.  Attach the gasket to the back of the backbox. 
2.  Mount the backbox with the gasket in the desired location 
using the four mounting screws provided. 
3.  Attach conduit and pull wiring into the backbox. 
4.  Install a conduit plug (provided) in unused conduit holes. 
5.  Wire the manual station using the figures in “Wiring 
diagrams” below. 
6.  Open the faceplate using the key provided. 
7.  Attach the switch and wiring plate to the backbox using the 
four 6-32 screws provided. Make sure to align the station’s 
mounting holes over the spacers provided in the backbox. 
8.  Install the glass rod in the back of the faceplate if it is 
required for use. 
See the note above, Figure 1, and “Replacing the glass 
rod” on page 2 for more details. 
9.  Close and lock the faceplate. 
Figure 1: MPSR features and installation 
 
Wiring diagrams 
Depending on which model of manual station you have, you 
could have either a two contact or six contact terminal block. 
See Figure 2 and Figure 3 for proper wiring of your manual 
station. 
Note: Contact ratings are shown with the manual station’s pull-
down handle in the closed position. 
Figure 2: Two contact terminal block wiring 
 
Faceplate with
pull handle
Switch and wiring plate
Gasket
6-32 screws
(provided)
Back box
mounting screws
Back box
Threaded
conduit holes
Conduit plugs
(provided)
Glass rod
installation slot