16
EGS Series Quick Start User Manual
Version 01 - 2020
Auto Application Setup Parameter Settings
Initial
Volts
Start
Time
Stop
Time
Trip
Class
Current
Limit
Current
Limit Time
Unit % s s - *FLC s
Default 20% 10 0 10 3.5 30
Heavy 40% 10 0 20 4 40
Agitator 30% 10 0 10 3.5 25
Compressor 1 40% 15 0 20 3.5 25
Compressor 2 35% 7 0 10 3.5 25
Conveyor Loaded 10% 10 7 20 5.5 30
Conveyor Unloaded 10% 10 7 10 3.5 30
Crusher 40% 10 0 30 3.5 60
Fan High Inertia 40% 10 0 30 3.5 60
Fan Low Inertia 30% 15 0 10 3.5 30
Grinder 40% 10 0 20 3.5 40
Mill 40% 10 0 20 3.5 40
Mixer 10% 10 0 20 4 25
Moulding M/C 10% 10 0 10 4.5 25
Press Flywheel 40% 10 0 20 3.5 40
Pump 1 10% 10 60 10 3.5 25
Pump 2 10% 10 60 20 3.5 25
PumpJack 40% 10 0 20 3.5 40
SawBand 10% 10 0 10 3.5 25
SawCircular 40% 10 0 20 3.5 40
Screen Vibrating 40% 10 0 20 4.5 40
Shredder 40% 10 0 30 3.5 60
Wood Chipper 40% 10 0 30 3.5 60
Compressor 1 = Centrifugal, Reciprocating, Rotary Screw
Compressor 2 = Rotary Vane, Scroll
Pump 1 = Submersible: Centrifugal, Rotodynamic
Pump 2 = Positive Displacement: Reciprocating, Rotary
Configuration and Parameters (continued)