17
EGS Series Quick Start User Manual
Version 01 - 2020
General Specification
Product Standard EN 60947-4-2: 2012
Rated operational voltages U
e
200Vac to 600Vac (See Key to part numbers)
Rated operational current I
e
See Rating Table
Rating index See Rating Table
Rated frequencies 50 - 60Hz ± 5Hz
Rated duty Uninterrupted.
Form designation Form 1, Internally Bypassed
Method of operation Symmetrically controlled starter
Method of control Semi-automatic
Method of connecting
Thyristors connected between motor windings
and supply
Number of poles
3 main poles, 2 main poles controlled by
semiconductor switching element
Rated insulation voltage U
i
Main circuit
See Key to part
numbers
Control supply circuit 230Vac r.m.s
1)
Rated impulse withstand voltage U
imp
Main circuit 6 kV
Control supply circuit 4 kV
1)
IP code
Main circuit
IP00 (IP20 with finger
guards
6
)
Supply and Control
circuit
IP20
Overvoltage Category / Pollution degree III / 3
Rated conditional short-circuit current and type of co-ordination
with associated short circuit protective device (SCPD)
Type 1 co-ordination
See Short Circuit Protection Tables for rated
conditional short-circuit current and required
current rating and characteristics of the associated
SCPD
Technical
Information/Specification
EEC EGS Series - Page 18