TECHNICAL
ASSISTANCE MANUAL
DMU Suite 1.3
DATA MONITOR UNIT
DMU
3000
DMU
2000
DMU
3000 PLUS

Questions and Answers

  • R
    Rachael GraySep 2, 2025
    Why does warning light 3 flash quickly during the first boom rise on my Effer DMU 3000 Industrial Equipment?
    • J
      Jean HudsonSep 2, 2025
      If warning light 3 flashes quickly during the first boom rise maneuver, and warning lights 1, 2, 4, and 7 are lit with a continuous alarm, the DMU is receiving an anomalous pressure value from the first boom cylinder. Replace the pressure transducer.
  • J
    jennifer08Aug 31, 2025
    What does it mean if warning light 2 flashes quickly and lights 1, 3, 4, and 7 are on with a continuous alarm on my Effer DMU 3000?
    • V
      Vanessa Wiggins MDAug 31, 2025
      If warning light 2 flashes quickly while lights 1, 3, 4, and 7 are permanently on with a continuous alarm, the DMU is receiving an anomalous pressure value from the second boom cylinder. Replace the pressure transducer.
  • E
    Edward AllenAug 29, 2025
    Why is warning light 1 flashing quickly while lights 2, 3, 4, and 7 are on with a continuous alarm on my Effer Industrial Equipment?
    • M
      millerkristinAug 29, 2025
      If warning light 1 flashes quickly and warning lights 2, 3, 4, and 7 are on permanently accompanied by a continuous alarm, the DMU is receiving an anomalous pressure value from the jib cylinder. Replace the pressure transducer.
  • W
    William GeorgeAug 28, 2025
    What does it mean if warning lights 1, 2, 3, 4, and 7 are flashing quickly with a continuous alarm on my Effer Industrial Equipment?
    • K
      Kevin DavisAug 28, 2025
      If warning lights 1, 2, 3, 4, and 7 are flashing quickly and a continuous acoustic alarm is sounding, it means a crane control bank lever is not in its central position because a microswitch is operated in both directions. Replace the faulty microswitch fitted to the control bank.
  • A
    Ann PattonAug 27, 2025
    What does it mean if warning light 3 flashes quickly and lights 1, 2, 4, and 7 are on with a continuous alarm on my Effer DMU 3000?
    • T
      Tonya PerezAug 27, 2025
      If warning light 3 flashes quickly while lights 1, 2, 4, and 7 are permanently on with a continuous alarm, the DMU isn't receiving a pressure value from the first boom cylinder. Replace the pressure transducer or restore the electric connection between the DMU and the pressure transducer.
  • B
    Brian GutierrezAug 25, 2025
    What to do if warning lights 1, 2, 3, 4, and 7 are flashing slowly with a continuous alarm on my Effer DMU 3000?
    • J
      jscottAug 25, 2025
      If warning lights 1, 2, 3, 4, and 7 are flashing slowly accompanied by a continuous acoustic alarm, the DMU is indicating that a crane control bank lever is not in the central position. This is due to a microswitch behind a control bank lever being operated. Replace the faulty microswitch fitted to the control bank.
  • J
    Jasmine MaldonadoAug 22, 2025
    Why does the jib load limiting device activate on my Effer DMU 3000 with a lower load than allowed?
    • R
      rsmithAug 23, 2025
      If the jib load limiting device activates with a load lower than allowed, the DMU is receiving an anomalous pressure value from the jib cylinder, higher than expected for the applied load. Replace the electronic card to resolve this issue.

Summary

Installing the DMU Software

Connecting the Computer to the Crane

Communication Port Settings

Changeable Parameters Explanation

Load Limiting Device Adjustments

Parameters for adjusting load limits and crane operation.

Boom, Jib & Downgrading Settings

Configuration settings for boom, jib, and performance downgrading.

Displaying and Changing Software Data

DMU Diagnostics Instructions

Sensors Diagnostic and DMU hardware

Analyzes sensors and DMU hardware for faults.

Control Bank Lever Diagnostics

Checks the functionality of the control bank levers.

Adjusting Angle Sensors

Entering New Parameters for Crane Configuration

Overload Test Procedure

DMU Diagnostics and Troubleshooting

Lever Operation Errors

Faults related to control bank lever position and operation.

Sensor Errors (Pressure & Angle)

Faults detected in pressure and angle sensors.

Communication and Connection Errors

Errors related to short circuits and communication failures.

Operational Blockage Errors

Errors causing crane blockage or specific warning light patterns.

Checking Wiring Functionality

Effer DMU 3000 Specifications

General IconGeneral
BrandEffer
ModelDMU 3000
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals