10


Cold loop test
          
ensure the following:
all power circuits are connected to the frequency converter as per technical
and operation manual, all power cables are correctly connected and
properly secured to their terminals;
all auxiliary equipment is connected to the frequency converter as per
technical and operation manuals for the frequency converter and respective
auxiliary equipment;
all communication circuits are connected to the frequency converter as per
technical and operation manual;
there are no short faults in the input/output communication and power
circuits, connected to the frequency converter;
frequency converter is properly grounded.
Commissioning and initial set-up
Initial power-up of the frequency converter should be performed with the
motor disconnected (disconnected output power cables). After energizing
the input power circuit and powering up the frequency converter, please
make sure there are no faults and that the frequency converter is in the
«STOP» mode. In the event of faults, please refer to the technical and
operation manual.
WARNING!
If the frequency converter has been out of operation for an extended
time (over 6 months), or if there has been a delay of more than 6 months
between the converter delivery and initial power-up, please power up the
converter with output power cables disconnected and keep it energized
for one hour. The frequency converter should remain in the «STOP» mode
for the duration of this period. This is required to properly reform the DC
capacitors of the frequency converter.
5 DELIVERY SCOPE
1. Frequency converter – 1 pc.;
2. Operation manual - 1 pc.;
3. Technical manual – 1 pc.;
4. External operator panel ribbon cable - 1 pc.;
5. External operator panel mounting frame - 1pc.