AEM33 P 485 User Manual
VT SET-UP
The default voltage setting is 400V and this value should not be altered unless the meter is an HV
type and is connected via voltage transformer(s). In this instance the nominal line to line voltage of
the meter must match the secondary voltage of the VT(s) and the voltage is programmed to the
primary voltage rating of the VT(s)
MD INTEGRATION PERIOD SET-UP (in Minutes)
This sets the integration period for the sliding window used for MD calculation.
Press the or key until the desired value is displayed.
Press the key to advance the page.
CURRENT / VOLTAGE AVERAGING PERIOD SET UP
This sets the integration period (in seconds) for the sliding window used for average current and
voltage calculations. Press the or key until the desired value is displayed.
Press the key to advance the page.
HOURS RUN SET-UP
The hours run preset level may be set to any desired kW value.
Press the or key until the desired value is displayed.
Press the key to advance the page.
PULSE SET-UP
The pulse rate value (PLr) may be set between 0.1 and 100 pulses per unit. Press the or key
until the desired pulse is displayed. Note that the unit of energy (Wh/kWh/MWh) will automatically
change to reflect the primary values of CT & VT previously set. The pulse value is set for both
outputs during the process. Press the key to store the value and advance the page.
The pulse duration value (PLt) may be set in increments between 100mS & 20 seconds as required.
The Pulse Output test allows the meter pulse output and connected data collection hardware to be
tested regardless of whether an actual load is present.
Press the button to start the test.
The display will show ‘run’ and the front panel led will flash to verify a pulse is being generated. The
display will verify the number of pulses generated.
Press the button to stop the test.
Press and simultaneously to reset the counter.
Press the key to advance the page.