RS485 SET-UP
This allows the baud rate and MODBUS address to be set. Use the and buttons to set the
desired baud rate. Press the key to store the value and advance the page.
Use the and buttons to set the unit address. Press the key to store the value and save and
exit from the set-up menu. The display will show ‘storing’ to confirm this action.
Technical Characteristics
3 Phase 3 or 4 wire Unbalanced,
3 Phase Balanced,
Single Phase Load
Voltage: 400/230V 3 Phase 3/4 wire
Current: 5A – External CTs. Fully isolated.
<0.1VA per phase Current/Voltage
Opto isolated volt free contact
Rating: 100mA ac/dc, 100V ac/dc max
Value: 1 pulse per kWh
1 pulse per 10 kWh
1 pulse per 100 kWh
1 pulse per 1000 kWh
Duration: 100ms.
Isolation: 2.5kV for 1 minute
Voltage x 4 for 1 hour
Current x 40 for 0.5 seconds max
Instrument = IP20
Front panel = IP40
kWh: Class 1 EN62053-21 7 BS8431
(2%-120% Nominal Load)
Operate -10oC > T < 65oC.
RH < 75% Non-Condensing
Storage- 25oC > T < 75oC
IP54 (IP65 with optional kit)