User Manual
EM303B General Purpose Inverter
9
1.1.2 EM303B Technical Specifications
Table 1-2 EM303B Technical specifications
3-phase 380VAC±20%, 50~60Hz±5%,
voltage imbalance rate <3%
3-phase, from 0 to U
supply
.
Model G: 150% rated current for 1 minutes, 180% rated
current for 10 seconds
Model P: 120% rated current for 1 minutes, 150% rated
current for 10 seconds
Frequency (Speed) input, torque input
Keypad, control terminals (2-wire sequence, 3-wire
sequence), RS485
Input Frequency Resolution
Numeric input: 0.01Hz, analog input: 0.1% of maximum
frequency
±0.2% rated synchronous speed
Acceleration/Deceleration Time
0.01~600.00 seconds/minutes
Rated output voltage: 20%~100% adjustable
Frequency base :20Hz~600Hz adjustable
Automatic torque boost, fixed torque boost curve,
customer defined V/F curve scaling
150%/1Hz(V/F),150%/0.5Hz(SVC)
AVR is active while output voltage remains unchanged if
input voltage is varying.
Automatically limit output current, avoid tripping
overcurrent
Brake frequency:0.1~60Hz, brake time:0~30S,
brake current:0~150% rated current
Communication, analog voltage, analog current, preset
speed, simple PLC and their combinations
Achieve textile wobbulation functions like wobbulation
range, time and jump
Function of
Input and
Output
Terminal Control Power Supply
7 programmable numeric input terminals
4 analog inputs:2 voltage inputs (0~10V), and 2 current
inputs(0~20mA)
2 OC outputs and 1 relay output are programmable.
Maximum output current of OC: 50mA. Relay contact
capacity: 250VAC/3A or 30VDC/1A. When relay acts,
EA-EC is on, and EB-EC is off.
2 programmable analog output terminals can output 0~10V
or 0~20mA
Human interactions with displays and control actuators
Upload and download parameter information of the
inverter, copy parameters rapidly.
Short circuit, overcurrent, overload, overvoltage,
undervoltage, phase loss, overheating, external fault, and
etc.
Indoor, with altitude less than 1000 meters, free from dust,
corrosive gas, and direct sunlight
-10℃~+40℃. In the temperature range +40 °C…+50 °C,
the rated output current is decreased by 1% for every
additional 1 °C. 20%~90%RH (no condensation)
Wall mounting, floor mounting, flush mounting