1.3 Prevention and elimination of malfunctions
If suspected that meter works improperly, the following actions should be performed:
1.3.1 Exterior inspection
Before applying voltage to the meter makes sure its case has no mechanical damages, there
are no signs of overheating, and all wires are properly connected.
Do not plug a meter into network if it is mechanically damaged. This can cause
staff injuries and destroy meter as well as other equipment!
Before switching on network voltage, it is necessary to check if sliding voltage
link is connected (see chapter 5.7 Sliding voltage link).
1.3.2 Inspection of connection and parametrization constants
Installing, uninstalling, parametrization and verification can be performed only by authorized
organizations that have qualified technicians. After plugging a meter into electric network
technician should check whether date and time are correct, whether meter shows right
energy direction, valid tariff time zone and calendar, tariff seasons.
1. If meter shows wrong date and time, a representative from the organization in charge of
the meter installation should be informed.
2. If LCD indicator shows a warning note ‘Er’, the meter should be uninstalled and passed
for repair works.
3. If energy direction is wrong, technician should check whether inputs are connected
properly to terminal block.
4. If meter calendar season, season time name or valid tariff time zone does not correspond
to real situation, meter’s parameterization data has to be checked and errors has to be
corrected by repeated meter’s parameterization.
1.3.3 Procedure of meter returning to manufacturer
In case malfunctions cannot be eliminated on the spot, the meter should be returned to the
manufacturer for repair or replacement. Meters on their return to manufacturer must have
their Passport with notices of organization in charge of their exploitation and short description
of meter’s malfunctioning.
1.3.4 Proper disposal of product
This sign indicates, that this product cannot be thrown out with any other
waste when its validity period is over if this sign is on the product or it is
included in product’s description. In order to prohibit possible harm for
environment and human health because of uncontrolled waste
elimination, please separate this product from other forms of waste, and
if it is possible use this product or its parts repeatedly in recycling
process. Home users can contact product manufacturer or local
administration for information about product utilization and recycling
without any harm to the environment. Enterprises must contact their own
providers to revise product’s validity terms and conditions stated in
purchase agreements. This product cannot be thrown out with any other
waste of different kind.