EasyManua.ls Logo

Elson 150zd - Installation General Procedures; Pipe Fitting Specifications; Cold Water Feed Requirements; Cold Water Combination Valve Assembly

Default Icon
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5
PIPEFITTINGS
Allpipettingsaremadevia22mmcompression
ttingsdirectlytotheunit.Thettingsarethreaded
3/4”BSPmaleparallel,shouldthreadedpipe
connectionsberequired.
COLDFEED
A22mmcoldwatersupplyisrecommended,however,
ifa15mm(1/2”)supplyexists,whichprovidessufcient
ow,thismaybeused(althoughmoreownoise
maybeexperienced).
Astopcockorservicingvalveshouldbeincorporated
intothecoldwatersupplytoenablethecylinderand
itsassociatedcontrolstobeisolatedandserviced.
COLDWATERCOMBINATIONVALVEASSEMBLY
The2-piececoldwatercombinationvalveassembly
(seeFig.2)canbelocatedanywhereonthecold
water mains supply prior to the expansion vessel
(seeFig.6Page10)butthetwopiecesdonothave
tobeinstalledtogether.
The pressure reducing valve incorporates the
pressure reducer and strainer and the expansion valve
incorporatestheexpansionandcheckvalves.Ensure
that the valves are installed in the correct order
andorientation.Noothervalvesshouldbeplaced
betweentheexpansionvalveandthecylinder.A
connectioncanbemadebetweentheexpansionand
pressurereducingvalvestoprovideabalancedcold
waterconnection.Theexpansionvalveconnection
mustnotbeusedforanyotherpurpose.
DRAIN TAP
Asuitabledrainingtapshouldbeinstalledinthecold
watersupplytothecylinderbetweentheexpansion
valve(seeFig.6Page10)andtheheaterataslowa
levelaspossible.Itisrecommendedthattheoutlet
pointofthedrainpipeworkbeatleast1metrebelow
theleveloftheheater(thiscanbeachievedby
attachingahosetothedraintapoutletspigot).
EXPANSIONVESSEL
The expansion vessel accommodates expansion
thatresultsfromheatingthewaterinsidetheunit.
Theexpansionvesselispre-chargedat0.35MPa
(3.5bar).Theexpansionvesselmustbeconnected
betweentheexpansionvalveandthecylinder(see
Fig.6Page10).Thelocationoftheexpansion
vessel should allow access to recharge the pressure
asandwhennecessary,thiscanbedoneusing
anormalcarfootpump.Itisrecommendedthat
theexpansionvesselisadequatelysupported.An
expansionvesselwallmountingbracketissupplied
forthispurposeandshouldbetted.
SECONDARYCIRCULATION
Ifsecondarycirculationisrequireditisrecommended
thatitbeconnectedtothecylinderasshown (see
Fig.3page5)via a swept tee joint into the cold
feedtotheunit.Asweptteejointisavailableasan
accessory(ordercodeno.5133565).
Thesecondaryreturnpipeshouldbein15mmpipe
andincorporateacheckvalvetopreventbackow.
AsuitableWRASapprovedbronzecirculation
pumpwillberequired.Onlargesystems,dueto
theincreaseinsystemwatercontent,itmaybe
necessarytotanadditionalexpansionvesseltothe
secondarycircuit.Thisshouldbedoneifthecapacity
ofthesecondarycircuitexceeds10litres.
Pipe capacity (copper):
15mmO.D.=0.13l/m(10litres=77m)
22mmO.D.=0.38l/m(10litres=26m)
28mmO.D.=0.55l/m(10litres=18m)
NOTE:SecondarycirculationisNOTrecommendedfor
directelectricunits.
OUTLET
Thehotwateroutletisa22mmcompressiontting
locatedatthetopofthecylinder.Hotwaterdistribution
pipeworkshouldbe22mmpipewithshortrunsof
15mmpipetoterminalttingssuchassinksand
basins.Pipesizesmayvaryduetosystemdesign.
INSTALLATION GENERAL
Fig.2:Coldwatercombinationvalveassembly
Fig.3:Secondarycirculationconnection

Related product manuals