4 Technical Specification
32 User’s Guide '(/7$23
7HFKQLFDO6SHFLILFDWLRQ
This chapter provides you with technical specification about '(/7$23
&RPPXQLFDWLRQ&KDQQHOV
PROGRAMMABLE TYPE APPLICATION
&20
9-pins D-Sub male
Yes
Serial RS232C
or RS485
RS485 is used for communications with
control panels in 0DVWHU6ODYH networks.
&20
9-pins D-Sub male
Yes
Serial RS232C
or RS485
RS232C is used for communications with
printers, computers, modems, pagers, etc.
&1
Terminal Block
Yes
Serial FTT-10
Control Panels in H%XV networks
(the use of .LWIRU23'$H%XV
&RPPXQLFDWLRQ%RDUG is required)
,QSXWV
TYPE NO.
ELECTRICAL DATA COMMENTS
+')$'HWHFWLRQ/LQH
&1
1 +24VDC Hardware Detection of Fire Alarm
2XWSXWV
TYPE NO.
ELECTRICAL DATA COMMENTS
3/0LPLF3DQHO
(delivered from
factory)
1 Max. 64 LED
Max 240 assignments
Max. 3 LED
Multiplexed Output
Programmable from control panel
Per assignment
3/)LUH%ULJDGH
(the use of ".LWIRU
23)LUH%ULJDGH
7HUPLQDWLRQ&DUG"
is required)
1 +24V or
NC-C-NO
Remote Fire Alarm
+24V or
NC-C-NO
Remote Fault Alarm
FBF Fire Brigade Panel Output
Monitored when coil voltage
outputs are selected
Compatible with German standard
6WRUDJH&DSDFLW\
PROGRAMMED IN →
EEPROM
EPROM RAM
Assignments Mimic Panel 240
Assignments Alarm Outputs 90
Log Messages 1000
3RZHU6XSSO\
TYPE
ELECTRICAL DATA COMMENTS
Voltage
Current
21 to 30 VDC
50-60mA, (normal mode)
300mA, (alarm mode)
Two monitored power supply inputs (CN1-3,4 and 5,6)
to be supplied via two different circuits, so that short-
circuiting one of them will not affect the other
2WKHU'DWD
Weight 1.7 kg Enclosure included
Storage Temperature -20 ºC to +70 ºC
Operating Temperature 0 ºC to +50 ºC
Humidity 0% to 95%
IP Rating 42 Engineered for indoors mounting
Dimensions 340x220x70 mm WxHxD