EasyManua.ls Logo

Eltek INV222 - 8.4 Dimensional Drawings

Eltek INV222
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DC/AC Inverter
INV222 & INV211
User Manual
Page 17 (20)
©2014. ELTEK DEUTSCHLAND GmbH.
Eltek_UM_INV222_and_INV211_E_R2.0.doc
Parallel operation
Parallel operation without any additional equipment and without fixed master
possible; max. 20 modules
2
, load sharing approx. 5% Inom due to decreasing
output characteristic
Communication
CAN-BUS interface to communicate with a static transfer switch STS
Isolated signaling contacts
“Collective Alarm”, relay contact NC; maximum contact load: 60 V/0.1 A
Ambient conditions:
Climatic conditions
Acc. to IEC 721-3-3 class 3K3/3Z1/3B1/3C2/3S2/3M2
Max. installation altitude
1500 m
Ambient temperature
Operation: -20 °C to +55 °C (power derating 2 %/K above +40 °C);
storage: -40 °C to +85 °C
Audible noise
45 dB (A) at 1 m distance
Mechanical:
Design ¼ x 19“ subrack, 2U, with connectors on the rear side
Cooling
Fan cooling (temperature regulated, monitored)
Surfaces
Powder coating RAL 7035 (front panel only), print: neutral, black RAL 9005; con-
structive parts: anodized metal
Dimensions (W/H/D)
106.4/88.4/335 mm (1/4 x 19”, 2U)
Minimum installation depth
400 mm plus 25.5 mm length of the module handle (module integrated in a spe-
cific assembly set 19’’ sub rack)
Weight
Approx. 3.5 kg
Electrical connectors
DC-Input , AC-Output and signals: DIN 41612-M-connector
Applicable standards:
CE conformity
Yes
Mechanical construction
Acc. to VDE 0160 edition 5.88 chapter 7.2.2
Protection class
IP20
RFI suppression / immunity
CE-label, (EN50081-1, EN55011/55022, EN50082-2, EN61000-4 part 2/3/4/5)
Compliance to safety stand-
ards
Acc. to EN60950-1, VDE0100 T410, VDE0110, EN60146 (class A)
8.4 Dimensional drawings
Figure 8. Module dimensions
2
INV211/222-48V/60V/110V: From hardware release 03; INV211/222-220V: From hardware release 02