Troubleshooting
83
Table 5-2. Troubleshooting table for the fieldbus protocol
Symptom Possible causes Solution
No
communication
with device.
The Field
Communicator is
connected to a
segment with DeltaV
and the device on
the same segment is
being commissioned
using DeltaV.
The Field Communicator is
unable to communicate with
this device until you go
offline and then back online.
Connected to a
segment in a
bench
configuration and
the Live Device
List remains
blank (even the
Field
Communicator
does not appear).
This issue is caused
by the speed at
which certain
LAS-enabled
devices are
attempting to run the
segment.
Establish communication by
putting the Field
Communicator on the
segment first and then
adding one or more devices.
By putting the Field
Communicator on first, it will
remain the LAS and control
the communication.
Unable to change
the address of a
device.
The Field
Communicator is
unable to change the
address of a device
that is currently the
LAS.
Establish communication by
putting the Field
Communicator on the
segment first and then
adding one or more devices.
By putting the Field
Communicator on first, it will
remain the LAS and allow
the address change.
The Field
Communicator
does not remain
the LAS on a
segment.
A host takes over as
the LAS.
When a host is established
on a segment, it will take
over as the LAS. No action
is required.
A backup LAS takes
over as the LAS. The
lower the address
and Slot Time of the
device, the more
likely this will occur.
See “Changing the Slot
Time” on page 76.