Status LED Status LED Description Status LED Troubleshooting Information
Green “POWER” Module has power Supply voltage is present at module terminals
Red “TRIP”
Thermostat demand
signal Y is present, but the
compressor is not running
1.Compressor protector is open
Check for high head pressure
Check compressor supply voltage
2.Outdoor unit power disconnect is open
3.Compressor circuit breaker or fuse(s) is open
4.Broken wire or connector is not making contact
5.High pressure switch open if present in system
6.Compressor contactor has failed open
Yellow “ALERT”
Flash Code 1
Long Run Time
Low Refrigerant Charge
Compressor is running
extremely long run cycles
1.Low refrigerant charge
2.Evaporator blower is not running
Check blower relay coil and contacts
Check blower motor capacitor
Check blower motor for failure or blockage
Check evaporator blower wiring and connectors
Check indoor blower control board
Check thermostat wiring for open circuit
3.Evaporator coil is frozen
Check for low suction pressure
Check for excessively low thermostat setting
Check evaporator airflow (coil blockages or return air filter)
Check ductwork or registers for blockage
4.Faulty metering device
Check TXV bulb installation (size, location and contact)
Check if TXV/fixed orifice is stuck closed or defective
5. Condenser coil is dirty
6. Liquid line restriction (filter drier blocked if present in
system)
7. Thermostat is malfunctioning
Check thermostat sub-base or wiring for short circuit
Check thermostat installation (location, level)
8. Compressor Second Stage Cooling Wiring (Except Part
# 543-0012-00)
Solenoid plug not connected
Y2 not wired
Yellow “ALERT”
Flash Code 2
System Pressure Trip
High Refrigerant Charge
Discharge pressure
out of limits or
compressor overloaded
1. High head pressure
Check high pressure switch if present in system
Check if system is overcharged with
refrigerant
Check for non-condensable in system
2. Condenser coil poor air circulation (dirty, blocked,
damaged)
3. Condenser fan is not running
Check fan capacitor
Check fan wiring and connectors
Check fan motor for failure or blockage
4. Return air duct has substantial leakage
Flash Code number corresponds to a number of LED flashes, followed by a pause and then repeated. TRIP
and ALERT LEDs flashing at same time means control circuit voltage is too low for operation.
LED Troubleshooting Information