Termination Resistor for XWEB300D
If XWEB300D is placed at the beginning or at the end of the line, please install its termination resistor by adding a jumper in position 2
(JMP2 on the back side of the unit). Do not add the jumper if XWEB300D is placed in the middle of the RS485 line.
Dixell XWEB300D Configuration For CoreSense
XWEB300D is compatible with ZX CDU if XWEB has the library of ZX controller CoreSense (controller) model.
Login into XWEB
Go to Information Information
If this is not present, follow the steps below.
Open Dixell website http://www.dixell.com/xweb300d-xweb500-xweb500d/eng/, then login (register required)
Go to Support System sw update XWEB300D XWEB500 XWEB500D
Download the upgrade package With your web-browser, login into XWEB
Go to Information System Update menu
Provide the XW5 patch le
Once le has been selected wait until the upgrade procedure ends (XWEB reboots)
Verify the installation ended successfully by checking into the menu
Go to Information Information for string
Log in again and set up the ZX CDU
Go to Conguration Devices drop-down menu
Go to Actions New
Enter device name in the Name eld (e.g. ZX CDU)
Select “XCM25D” in the Model eld
Enter the ModBUS address in the RS 485 address eld
∙ Refer to setting of parameter “t01” in pr2 level in CoreSense
(default setting is “1”)
Click New