Step Action Phenomenon and Description
1
Press “
” > 3 seconds
Press “
together.
2
Press “
” or “
Modify the number for Target Evaporating Temperature
3
Press “
Press “
Evaporating Temperature (ZXD Only)
Jumper received with the unit
Jumper to be installed
Jumper after installation
Change the condensing temperature setpoint (E39) from 20°C to 35°C for R134a operation as below
Step Action Phenomenon and Description
1
Press “
” + “
Enter menu to select “PAr” (parameter) or “rtC”
2
Press “
” or “
Select“PAr (parameter)”
3
Press “
4
Press “
” or “
Browse to parameter E39
5
Press “
6
Press “
” or “
Change the set point from existing 20°C to 35°C
7
Press “
8
Press “
” + “
Exit (or exit automatically after waiting for 120 seconds)
Now the unit is ready for operation with R134a Refrigerant.