1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx iProCHILL 122/205
ST 9
Chiller temperature control probe
0 - evaporator input NTC
1 - Evaporator output 1 NTC
2 - Evaporator output 2 NTC
3 - Evaporator output 3 NTC
4 - Evaporator output 4 NTC
5 - Evaporator common output NTC
0
7
ST 10
Heat pump temperature control probe
0 - evaporator input NTC
1 - Evaporator output 1 NTC
2 - Evaporator output 2 NTC
3 - Evaporator output 3 NTC
4 - Evaporator output 4 NTC
5 - Evaporator common output NTC
8 - condenser water common input NTC
9 - circuit 1 condenser water input NTC
10 - circuit 2 condenser water input NTC
11 - circuit 3 condenser water input NTC
12 - circuit 4 condenser water input NTC
13 - circuit 1 condenser water output NTC
14 - circuit 2 condenser water output NTC
15 - circuit 3 condenser water output NTC
16 - circuit 4 condenser water output NTC
17 - condenser water common output NTC
WARNING
If the same temperature control is required in cooling and heating mode, set
the same value in the ST09 and ST10 parameters
0
17
ST 11
Defines the type of temperature control
0 = Proportional
2 = Neutral zone
0
4
ST 12
Defines the temperature control logic
0 = Of machine
1 = on two separate circuits
0
1
Circuit 2 regulation if temperature control is enabled on two separate circuits
ST 13
Circuit 2 chiller set point
This allows you to set the working set point in chiller mode
ST14
ST15
°C/°F
dec/int
ST 14
Circuit 2 chiller minimum set point
This defines the minimum limit that can be used to set the working set
point in chiller mode
-50.0
-58
ST15
°C
°F
Dec
int
ST 15
Circuit 2 chiller maximum set
This defines the maximum limit that can be used to set the working set
point in chiller mode
ST14
110
230
°C
°F
Dec
int
ST 16
Circuit 2 heat pump set point
This allows you to set the working set point in h.p. mode
ST17
ST18
°C/°F
dec/int
ST 17
Circuit 2 heat pump minimum set point
This defines the minimum limit that can be used to set the working set
point in heat pump mode
-50.0
-58
ST18
°C
°F
Dec
int
ST 18
Circuit 2 heat pump maximum set point
This defines the maximum limit that can be used to set the working set
point in heat pump mode
ST17
110
230
°C
°F
Dec
int
ST 19
Intervention band regulation steps of circuit 2 in chiller mode
0.1
1
25.0
45
°C
°F
Dec
int
ST 20
Intervention band regulation steps in circuit 2 heat pump
0.1
1
25.0
45
°C
°F
Dec
int
ST 21
Circuit 2 chiller temperature control probe
0 - evaporator input NTC
1 - Evaporator output 1 NTC
2 - Evaporator output 2 NTC
3 - Evaporator output 3 NTC
4 - Evaporator output 4 NTC
5 - Evaporator common output NTC
0
7