1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx iProCHILL 130/205
PA 17
Condenser pump operation mode
0 = Absent (pump not controlled).
1 = Continuous operation: the pump being switched on and off is linked with
the unit being switched on and off.
2 = Working on demand of the compressors: pump switch-on and off is
linked with the compressors being switched on and off.
0
2
PA 18
Compressor ON delay from condenser pump start-up
0
250
Sec
10 Sec
PA 19
Condenser pump OFF delay from compressor shut off
0
250
Sec
10 Sec
PA 20
Deactivation pump delay from when the unit is switched off
0
250
Sec
10 Sec
PA 21
Pump activation and rotation:
0 = No Rotation;
1 = Manual Rotation;
2 = Start Rotation;
3 = Rotation at Hours;
4 = Rotation at Start and Hours
0
4
PA 22
Manual pump inversion:
0 = Pump 1 On;
1 = Pump 2 On
0
1
PA 23
No. of hours for forced condenser pump rotation
0
999
Hr
10Hr
PA 24
Simultaneous pump running time after forced condenser pump rotation
0
250
Sec
Condenser water pump operation with anti-freeze alarm
PA 25
Condenser water pump/s anti-freeze operation when the device is OFF or on
Stand-by
0 = always OFF in remote OFF or Stand-by
1 = ON, parallel with the anti-freeze heaters
2 = on in remote OFF or Stand-by, depending on the temperature control
request
0
2
PA 26
Condenser anti-freeze temperature control probe alarm
0 = disabled
1 = common condenser water input probe
2 = common condenser water input probe and condenser input 1/2
3 = common condenser water input probe and condenser input 3/4
4 = condenser water output probe 1/2
5 = condenser water output probe 3/4
6 = condenser output 1/2/3/4
7 = condenser output 1/2/3/4 and common output
8 = external air temperature
0
8
PA 27
Condenser water pump activation set point in anti-freeze mode on the
temperature control probe
-50.0
-58
110
230
°C
°F
Dec
int
PA 28
Condenser water pump differential deactivation in anti-freeze mode on the
temperature control probe
0.1
1
25.0
45
°C
°F
Dec
int
Condenser water pump maintenance request
PA 29
Condenser pump timer setting
0
999
Hr
10 Hr
PA 30
Condenser no. 2 pump timer setting
0
999
Hr
10 Hr
Pump down function
Pump down
Pd 1
Pump down operation
0= function disabled
1= disabled with pump down
2= disabled and enabled with pump down
3= disabled with pump down only in chiller mode
4= enabled with pump down and disabled with pump down only in chiller
mode
0
4
Pd 2
Pump down pressure setting (see pump down chapter)
0.0
0
50.0
725
Bar
psi
Dec
int
Pd 3
Pump down pressure differential (see pump down chapter)
0.1
1
14.0
203
Bar
Psi
Dec
int
Pd 4
Maximum time in Pump down when started-up and stopped (see pump down
chapter)
0
250
Sec
Timed pump down
Pd 5
Pump down time upon start-up
0 = function disabled
0
250
Sec
Pd 6
Pump down time upon shutdown
0 = function disabled
0
250
Sec
Pump down alarm
Pd 7
Maximum number of pump down alarm interventions per hour, at stopped.
When exceeded, the alarm is recorded and displayed on the
screen with a code and the relay alarm + buzzer is activated
Reset is always manual if Pd7 = 0
Reset is always automatic if Pd7 =60
Reset switches from automatic to manual if Pd7 falls between 1 and 59
0
60