Maximum number of pump down alarm interventions per hour, at started-up.
Exceeding this limit, the alarm must be reset manually, it will be saved in
the log and the alarm relay + buzzer will be activated
Reset is always manual if Pd8 = 0
Reset is always automatic if Pd8 =60
Reset switches from automatic to manual if Pd8 falls between 1 and 59
and based on the configuration of Par. Pd9
Pump down alarm automatic or manual reset activation upon start-up
0= the alarm remains in automatic reset even if the number of
interventions per hour is met
1=enables manual reset when the number of interventions per hour is
met
Evaporator water high temperate unloading
Comp. unloading set point of the evaporator input high water temperature in
chiller mode
Compressor unloading differential from the evaporator input high water
temperature
Delay for the compressor unloading function to be inserted by an evaporator
input high water temperature
MAX time in compressor unloading function by an evaporator input high water
temperature
Analogue input configuration for control of the unloading function of the
evaporator high water temperature
Evaporator water low temperate unloading
Compressor unloading set point from the evaporator low water temperature
Compressor unloading differential from the evaporator low water temperature
Delay for the compressor unloading function to be inserted by an evaporator
input low water temperature
MAX time in compressor unloading status due to the evaporator low water
temperature
Analogue input configuration for control of the unloading function of the
evaporator low water temperature
Chiller condensation unloading
Condensing temperature/pressure compressor unloading set point
Condensing temperature/pressure compressor unloading differential
Evaporation pressure compressor unloading set point
Evaporation pressure compressor unloading differential
MAX time in temperature / pressure compressor unloading status
Choice of steps for circuit to insert in unloading mode
Fan regulation
0= absent
1= always ON
2 =ON/OFF step insertion
3= continuous ON/OFF step insertion
4= speed proportional regulator
Fan working mode
0= depending on the compressor
1= independent from the compressor
MAX speed fan peak time after ON (TRIAC) At every start-up the fan is
powered at maximum voltage for time FA03, irrespective of the
condensation temperature/pressure. When this elapses, the fan
continues at the speed set by the regulator.
Fan phase displacement analog output 5 (only if configured as PWM /
phase cut)
Fan phase displacement analog output 6 (only if configured as PWM /
phase cut)