1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx iProCHILL 131/205
Pd 8
Maximum number of pump down alarm interventions per hour, at started-up.
Exceeding this limit, the alarm must be reset manually, it will be saved in
the log and the alarm relay + buzzer will be activated
Reset is always manual if Pd8 = 0
Reset is always automatic if Pd8 =60
Reset switches from automatic to manual if Pd8 falls between 1 and 59
and based on the configuration of Par. Pd9
0
60
Pd 9
Pump down alarm automatic or manual reset activation upon start-up
0= the alarm remains in automatic reset even if the number of
interventions per hour is met
1=enables manual reset when the number of interventions per hour is
met
0
1
Unloading Function
Evaporator water high temperate unloading
Un 1
Comp. unloading set point of the evaporator input high water temperature in
chiller mode
-50.0
-58
110.0
230
°C
°F
Dec
int
Un 2
Compressor unloading differential from the evaporator input high water
temperature
0.1
0
25.0
45
°C
°F
Dec
int
Un 3
Delay for the compressor unloading function to be inserted by an evaporator
input high water temperature
0
250
Sec
10 sec
Un 4
MAX time in compressor unloading function by an evaporator input high water
temperature
0
250
Min
Un 5
Analogue input configuration for control of the unloading function of the
evaporator high water temperature
1
51
Evaporator water low temperate unloading
Un 6
Compressor unloading set point from the evaporator low water temperature
-50.0
-58
110.0
230
°C
°F
Dec
int
Un 7
Compressor unloading differential from the evaporator low water temperature
0.1
0
25.0
45
°C
°F
Dec
int
Un 8
Delay for the compressor unloading function to be inserted by an evaporator
input low water temperature
0
250
Sec
10 sec
Un 9
MAX time in compressor unloading status due to the evaporator low water
temperature
0
250
Min
Un 10
Analogue input configuration for control of the unloading function of the
evaporator low water temperature
1
51
Chiller condensation unloading
Un 11
Condensing temperature/pressure compressor unloading set point
-50.0
-58
0.0
0
110.0
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
Un 12
Condensing temperature/pressure compressor unloading differential
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
Evaporation unloading
Un 13
Evaporation pressure compressor unloading set point
-1.0
-14
50.0
725
Bar
Psi
Dec
int
Un 14
Evaporation pressure compressor unloading differential
0.1
1
14.0
203
Bar
Psi
Dec
int
Un 15
MAX time in temperature / pressure compressor unloading status
0
250
Min
Un 16
Choice of steps for circuit to insert in unloading mode
1
8
Un 17
Not used
Condensing fan
Parameter
Description
min
max
um
Resolution
FA1
Fan regulation
0= absent
1= always ON
2 =ON/OFF step insertion
3= continuous ON/OFF step insertion
4= speed proportional regulator
0
4
FA2
Fan working mode
0= depending on the compressor
1= independent from the compressor
0
1
FA3
MAX speed fan peak time after ON (TRIAC) At every start-up the fan is
powered at maximum voltage for time FA03, irrespective of the
condensation temperature/pressure. When this elapses, the fan
continues at the speed set by the regulator.
0
250
Sec
FA4
Fan phase displacement analog output 5 (only if configured as PWM /
phase cut)
0
8
micro
sec
250s
FA5
Fan phase displacement analog output 6 (only if configured as PWM /
phase cut)
0
8
micro
sec
250s