1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx iProCHILL 133/205
Proportional regulation
Set temperature / pressure for maximum fan speed in h.p. mode. This
allows you to set the condensation temperature / pressure value in h.p.
mode that corresponds to minimum fan speed.
Step regulation
SET 4th STEP This allows you to set the condensation temperature /
pressure value in heat pump mode that corresponds to the operation of
the relay output in ON configured as the 4th condensation fan speed
step.
Proportional regulation
Set temperature / pressure for minimum fan speed in h.p. mode. This
allows you to set the condensation temperature / pressure value in h.p.
mode that corresponds to maximum fan speed.
Step regulation
SET 3rd STEP This allows you to set the condensation temperature /
pressure value in heat pump mode that corresponds to the operation of
the relay output in ON configured as the 3rd condensation fan speed
step.
Proportional regulation
Proportional band regulation of fans in heat pump mode This allows you
to set a temperature / pressure differential that corresponds to a variation
from minimum to maximum fan speed.
Step regulation
With Par. FA01=2/3 becomes the differential on the step itself of circuit 1
in heat pump (see fans regulation graph).
Proportional regulation
Differential CUT- OFF in heat pump. This allows you to set a temperature
/ pressure differential in h.p. mode to shut off the fan.
Step regulation
With Par. FA01=2/3 becomes the differential on the step itself of circuit 2
in heat pump mode (see fans regulation graph).
Over ride CUT- OFF in h.p. This allows you to set a temperature /
pressure differential in h.p. mode, where the fan maintains minimum
speed.
Night function speed in HP mode. This allows you to set a maximum value for
the proportional regulation of the fans in h.p. It is expressed as a
percentage of the maximum voltage allowed.
Condensation fan step 3 / 4 in chiller mode
Third step setting in chiller mode
SET 3rd STEP This allows you to set the condensation temperature /
pressure value in chiller mode that corresponds to the operation in ON of
the relay output, configured as the 3rd condensation fan speed step.
Fourth step setting in chiller mode
SET 4th STEP This allows you to set the condensation temperature /
pressure value in chiller mode that corresponds to operation in ON of the
relay output, configured as the 4th condensation fan speed step.
Differential on circ.3 steps in chiller mode
With Par. FA01=2/3 becomes the differential on the step itself of circuit
3 chiller (see fans regulation graph).
Differential on circ.4 steps in chiller mode
With Par. FA01=2/3 becomes the differential on the step itself of circuit
4 chiller (see fans regulation graph).
Condensation fan step 3 / 4 in heat pump mode
SET 2nd STEP This allows you to set the condensation temperature /
pressure value in heat pump mode that corresponds to the operation of
the relay output in ON configured as the 2nd condensation fan speed
step.
SET 1st STEP This allows you to set the condensation temperature /
pressure value in heat pump mode that corresponds to the operation of
the relay output in ON configured as the 1st condensation fan speed
step.
Differential on circ.3 steps in HP mode
With Par. FA01 = 2 / 3 becomes the differential on the step itself of circuit
3 in heat pump mode (see fans regulation graph).
Differential on circ.4 steps in HP mode
With Par. FA01 = 2 / 3 becomes the differential on the step itself of circuit
4 heat pump mode (see fans regulation graph).
Operation in defrost (dF33 = 2)