1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx iProCHILL 133/205
FA19
Proportional regulation
Set temperature / pressure for maximum fan speed in h.p. mode. This
allows you to set the condensation temperature / pressure value in h.p.
mode that corresponds to minimum fan speed.
Step regulation
SET 4th STEP This allows you to set the condensation temperature /
pressure value in heat pump mode that corresponds to the operation of
the relay output in ON configured as the 4th condensation fan speed
step.
-50.0
-58
0.0
0
110
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
FA20
Proportional regulation
Set temperature / pressure for minimum fan speed in h.p. mode. This
allows you to set the condensation temperature / pressure value in h.p.
mode that corresponds to maximum fan speed.
Step regulation
SET 3rd STEP This allows you to set the condensation temperature /
pressure value in heat pump mode that corresponds to the operation of
the relay output in ON configured as the 3rd condensation fan speed
step.
-50.0
-58
0.0
0
110
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
FA21
Proportional regulation
Proportional band regulation of fans in heat pump mode This allows you
to set a temperature / pressure differential that corresponds to a variation
from minimum to maximum fan speed.
Step regulation
With Par. FA01=2/3 becomes the differential on the step itself of circuit 1
in heat pump (see fans regulation graph).
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
FA22
Proportional regulation
Differential CUT- OFF in heat pump. This allows you to set a temperature
/ pressure differential in h.p. mode to shut off the fan.
Step regulation
With Par. FA01=2/3 becomes the differential on the step itself of circuit 2
in heat pump mode (see fans regulation graph).
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
FA23
Over ride CUT- OFF in h.p. This allows you to set a temperature /
pressure differential in h.p. mode, where the fan maintains minimum
speed.
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
FA24
Night function speed in HP mode. This allows you to set a maximum value for
the proportional regulation of the fans in h.p. It is expressed as a
percentage of the maximum voltage allowed.
FA17
FA18
%
Condensation fan step 3 / 4 in chiller mode
FA25
Third step setting in chiller mode
SET 3rd STEP This allows you to set the condensation temperature /
pressure value in chiller mode that corresponds to the operation in ON of
the relay output, configured as the 3rd condensation fan speed step.
-50.0
-58
0.0
0
110
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
FA26
Fourth step setting in chiller mode
SET 4th STEP This allows you to set the condensation temperature /
pressure value in chiller mode that corresponds to operation in ON of the
relay output, configured as the 4th condensation fan speed step.
-50.0
-58
0.0
0
110
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
FA27
Differential on circ.3 steps in chiller mode
With Par. FA01=2/3 becomes the differential on the step itself of circuit
3 chiller (see fans regulation graph).
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
FA28
Differential on circ.4 steps in chiller mode
With Par. FA01=2/3 becomes the differential on the step itself of circuit
4 chiller (see fans regulation graph).
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
Condensation fan step 3 / 4 in heat pump mode
FA29
SET 2nd STEP This allows you to set the condensation temperature /
pressure value in heat pump mode that corresponds to the operation of
the relay output in ON configured as the 2nd condensation fan speed
step.
-50.0
-58
0.0
0
110
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
FA30
SET 1st STEP This allows you to set the condensation temperature /
pressure value in heat pump mode that corresponds to the operation of
the relay output in ON configured as the 1st condensation fan speed
step.
-50.0
-58
0.0
0
110
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
FA31
Differential on circ.3 steps in HP mode
With Par. FA01 = 2 / 3 becomes the differential on the step itself of circuit
3 in heat pump mode (see fans regulation graph).
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
FA32
Differential on circ.4 steps in HP mode
With Par. FA01 = 2 / 3 becomes the differential on the step itself of circuit
4 heat pump mode (see fans regulation graph).
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
Int
Operation in defrost (dF33 = 2)