Minimum fan speed in defrost mode. This allows you to set a
minimum value for proportional regulation of the fans in defrost
mode. It is expressed as a percentage of the maximum voltage
allowed.
Maximum fan speed in defrost mode. This allows you to set a
maximum value for proportional regulation of the fans in defrost
mode. It is expressed as a percentage of the maximum voltage
allowed.
Proportional regulation
Set maximum fan speed temperature/pressure in defrost mode. This
allows you to set the condensation temperature / pressure value in
defrost mode that corresponds to the minimum fan speed.
Step regulation
SET 4th STEP This allows you to set the condensation temperature /
pressure value in defrost mode that corresponds to operation in ON
of the relay output, configured as the 4th condensation fan speed
step.
Proportional regulation
Set minimum fan speed temperature/pressure in defrost mode. This
allows you to set the condensation temperature / pressure value in
defrost mode that corresponds to the maximum fan speed.
Step regulation
SET 3rd STEP This allows you to set the condensation temperature /
pressure value in defrost mode that corresponds to operation in ON
of the relay output, configured as the 3rd condensation fan speed
step.
Proportional regulation
Proportional band regulation of fans in defrost. This allows you to set a
temperature / pressure differential that corresponds to a variation from
minimum to maximum fan speed.
Step regulation
With Par. FA01=2/3 becomes the differential on the step itself of circuit 1
in defrost mode (see fans regulation graph).
Proportional regulation
Differential CUT- OFF in defrost. This allows you to set a temperature /
pressure differential in defrost mode to shut off the fan.
Step regulation
With Par. FA01=2/3 becomes the differential on the step itself of circuit 2
in defrost mode (see fans regulation graph).
Over ride CUT- OFF in defrost. This allows you to set a temperature /
pressure differential in defrost where the fan maintains minimum speed.
Night function speed in defrost mode. This allows you to set a
maximum value for proportional regulation of the fans in defrost
mode. It is expressed as a percentage of the maximum voltage
allowed.
Third step setting in defrosting mode
SET 2nd STEP This allows you to set the condensation temperature /
pressure value in defrost mode that corresponds to relay output operation
in ON configured as the 2nd condensation fan speed step.
Fourth step setting in defrosting mode
SET 1st STEP This allows you to set the condensation temperature /
pressure value in defrost mode that corresponds to relay output operation
in ON configured as the 1st condensation fan speed step.
Differential on circ.3 steps in defrosting mode
With Par. FA01=2/3 becomes the differential on the step itself of circuit
3 defrost mode
Differential on circ.4 steps in defrosting mode
With Par. FA01=2/3 becomes the differential on the step itself of circuit
4 defrost mode
Anti-freeze heaters – support
Antifreeze/support heaters (air/air units) set point in chiller mode.
The temperature value below which the heaters start up.
Anti-freeze/support heaters band regulation in chiller mode
Antifreeze/support heaters (air/air units) set point in heat pump mode
The temperature value below which the heaters start up.
Anti-freeze/support heaters band regulation in heat pump mode