1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx iProCHILL 135/205
Anti-freeze/support heaters operation in defrosting mode
0 = activated according to temperature control demand
1 = activated according to temperature control demand and during defrost
cycle
Anti-freeze/support heaters alarm temperature control probe in chiller
mode
0 = disabled
1 = evaporator input
2 = evaporator output 1 / 2
3 = evaporator output 3 / 4
4 = evaporator output 1 / 2 / 3 / 4
5 = evaporator output 1 / 2 / 3 / 4 and common output
Anti-freeze/support heaters temperature control probe in heat pump
mode
0 = disabled
1 = evaporator input
2 = evaporator output 1 / 2
3 = evaporator output 3 / 4
4 = evaporator output 1 / 2 / 3 / 4
5 = evaporator output 1 / 2 / 3 / 4 and common output
Condenser anti-freeze heaters temperature control probe
0 = disabled
1 = common condenser water input probe
2 = common condenser water input probe and condenser input 1 / 2
3 = common condenser water input probe and condenser input 3 / 4
4 = condenser water output probe 1 / 2
5 = condenser water output probe 3 / 4
6 = condenser output 1 / 2 / 3 / 4
7 = condenser output 1 / 2 / 3 / 4 and common output
Determines the evaporator/condenser anti-freeze heaters function if a probe
that is set to control them malfunctions
0 = OFF if the probe malfunctions
1 = ON if the probe malfunctions
Determines the anti-freeze heaters operation when the device is in chiller or
heat pump mode.
0 = always OFF (chiller and h.p.)
1 = ON only in chiller mode, depending on the temperature control
request
2 = ON only in h.p. mode, depending on the temperature control request
3 = ON in chiller and h.p. mode, depending on the temperature control
request
Determines the evaporator/condenser anti-freeze heaters operation
depending on the remote Off Stand-by mode
0 = Always OFF
1 = ON via temperature control
Defrost mode:
0 = defrost disabled
1 = temperature / pressure
2 = starts according to the value of parameter dF28 and ends according
to the time
3 = starts according to the value of parameter dF28 and ends due to an
external contact
4 = with a condensation fan
Defrost begins by temperature/pressure
Defrost ends by temperature/pressure
Defrost delay between two circuits
Idle time in compressor OFF mode before defrosting
Idle time in compressor OFF mode after defrosting
Defrost interval in the same circuit
Defrosting cycle start temperature setting together with circuit 1 after the
count of parameter dF09 elapses
Defrosting cycle start temperature setting together with circuit 2 after the
count of parameter dF09 elapses
Defrosting cycle start temperature setting together with circuit 3 after the
count of parameter dF09 elapses