Ar 5
Anti-freeze/support heaters operation in defrosting mode
0 = activated according to temperature control demand
1 = activated according to temperature control demand and during defrost
cycle
0
1
Ar 6
Anti-freeze/support heaters alarm temperature control probe in chiller
mode
0 = disabled
1 = evaporator input
2 = evaporator output 1 / 2
3 = evaporator output 3 / 4
4 = evaporator output 1 / 2 / 3 / 4
5 = evaporator output 1 / 2 / 3 / 4 and common output
0
5
Ar 7
Anti-freeze/support heaters temperature control probe in heat pump
mode
0 = disabled
1 = evaporator input
2 = evaporator output 1 / 2
3 = evaporator output 3 / 4
4 = evaporator output 1 / 2 / 3 / 4
5 = evaporator output 1 / 2 / 3 / 4 and common output
0
5
Ar 8
Condenser anti-freeze heaters temperature control probe
0 = disabled
1 = common condenser water input probe
2 = common condenser water input probe and condenser input 1 / 2
3 = common condenser water input probe and condenser input 3 / 4
4 = condenser water output probe 1 / 2
5 = condenser water output probe 3 / 4
6 = condenser output 1 / 2 / 3 / 4
7 = condenser output 1 / 2 / 3 / 4 and common output
0
7
Ar 9
Determines the evaporator/condenser anti-freeze heaters function if a probe
that is set to control them malfunctions
0 = OFF if the probe malfunctions
1 = ON if the probe malfunctions
0
1
Ar 10
Determines the anti-freeze heaters operation when the device is in chiller or
heat pump mode.
0 = always OFF (chiller and h.p.)
1 = ON only in chiller mode, depending on the temperature control
request
2 = ON only in h.p. mode, depending on the temperature control request
3 = ON in chiller and h.p. mode, depending on the temperature control
request
0
3
Ar 11
Determines the evaporator/condenser anti-freeze heaters operation
depending on the remote Off Stand-by mode
0 = Always OFF
1 = ON via temperature control
0
1
Defrost
Parameter
Description
min
max
um
Resolution
dF 1
Defrost mode:
0 = defrost disabled
1 = temperature / pressure
2 = starts according to the value of parameter dF28 and ends according
to the time
3 = starts according to the value of parameter dF28 and ends due to an
external contact
4 = with a condensation fan
0
4
dF 2
Defrost begins by temperature/pressure
-50.0
-58
0.0
0
110
230
50.0
725
°C
°F
bar
psi
Dec
int
Dec
Int
dF 3
Defrost ends by temperature/pressure
-50.0
-58
0.0
0
110
230
50.0
725
°C
°F
bar
psi
Dec
int
Dec
Int
dF 4
Minimum defrost duration
0
250
Sec
dF 5
Maximum defrost duration
1
250
Min
dF 6
Defrost delay between two circuits
0
250
Min
dF 7
Idle time in compressor OFF mode before defrosting
0
250
Sec
dF 8
Idle time in compressor OFF mode after defrosting
0
250
Sec
dF 9
Defrost interval in the same circuit
1
99
Min
dF 10
Defrosting cycle start temperature setting together with circuit 1 after the
count of parameter dF09 elapses
-50.0
-58
110
230
°C
°F
Dec
Int
dF 11
Defrosting cycle start temperature setting together with circuit 2 after the
count of parameter dF09 elapses
-50.0
-58
110
230
°C
°F
Dec
Int
dF 12
Defrosting cycle start temperature setting together with circuit 3 after the
count of parameter dF09 elapses
-50.0
-58
110
230
°C
°F
Dec
Int