dF 13
Defrosting cycle start temperature setting together with circuit 4 after the
count of parameter dF09 elapses
-50.0
-58
110
230
°C
°F
Dec
int
dF 14
End temperature setting of circuit 1 with defrost cycle
The actual defrost cycle on circuit 1 terminates when the temperature sensed
by the combined defrost temperature probe exceeds the dF14 limit.
-50.0
-58
110
230
°C
°F
Dec
int
dF 15
End temperature setting of circuit 2 with defrost cycle
-50.0
-58
110
230
°C
°F
Dec
int
dF 16
End temperature setting of circuit 3 with defrost cycle
-50.0
-58
110
230
°C
°F
Dec
int
dF 17
End temperature setting of circuit 4 with defrost cycle
-50.0
-58
110
230
°C
°F
Dec
int
dF 18
Forcing by switching ON activates all steps in defrosting mode in circuit 1
0 = disabled
1 = enabled
0
1
dF 19
Forcing by switching ON activates all steps in defrosting mode in circuit 2
0
1
dF 20
Forcing by switching ON activates all steps in defrosting mode in circuit 3
0
1
dF 21
Forcing by switching ON activates all steps in defrosting mode in circuit 4
0
1
dF 22
ON delay between two compressors in defrosting mode
1
250
Sec
dF 23
Fan ON activation during defrosting/dripping
0 = disabled
1 = enabled only during defrost
2 = enabled during defrosting/dripping
0
2
dF 24
Temperature/pressure setting that forces the fan ON in defrosting mode
-50.0
-58
0.0
0
110
230
50.0
725
°C
°F
bar
psi
Dec
int
Dec
Int
Defrost with condensation fans
dF 25
Defrost activation setting with condensation fans
The function defrost with outdoor fans is enabled if the external temperature
is above the dF25 level.
-50.0
-58
110
230
°C
°F
Dec
int
Defrost Start/Stop
dF 26
Defrosting cycle start in unit
0 = independent
1 = if both have reached the request for defrosting to start
2 = if at least one has reached the request for defrosting to start
0
2
dF 27
Defrosting cycle end in unit
0 = independent
1 = if both have reached the defrost end status
2 = if at least one has reached the defrost end status
0
2
Begin end defrost from analog input
dF 28
Probe that determines the defrost start and end
0= start and end with condensation temperature / pressure probe
1= start with evaporation pressure probe - end with condensation
temperature / pressure probe
2= start with condensation temperature / pressure probe - end with
evaporation pressure probe
3= start and end by evaporation pressure
4=start and end by auxiliary probe 1
0
4
Forced defrost
dF 29
Minimum idle time before forced defrosting
The device wait the delay time dF29 before starting a forced defrost cycle
after the relevant conditions have reached
0
250
Sec
dF 30
Forced defrosting temperature/pressure setting
-50.0
-58
0.0
0
110
230
50.0
725
°C
°F
bar
psi
Dec
int
Dec
Int
dF 31
Forced defrosting differential
0.1
1
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
Supply fan working in defrost mode
dF 32
Supply fan block in defrosting mode
0 = Not enabled Supply fan works during defrost
1 = Enabled Supply fan doesn’t work during defrost
0
1
Anti-freeze security for multi circuit units
dF 33
Forcing circuits that are not defrosting ON
0 function is disabled
1 function is enabled with the fan off
2 function is enabled with fan controlled by HP circuit
0
2