1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx iProCHILL 137/205
rC 1
Recovery function
0 = Disabled
1 = separate hydraulic circuits
2 = hydraulic circuits in parallel
3 = total recovery gas side
0
3
rC 2
Choice of recovery function priority
0 = user side
1 = recovery side
0
1
rC 3
Forced step deactivation time
0
250
Sec
rC 4
Forced step deactivation time after rotation of recovery valve
0
250
Sec
rC 5
Minimum operation time in recovery mode
Minimum activation time of heat recovery function once enabled
0
250
Min
rC 6
Minimum delay between recovery end and next recovery
Minimum time between disabling and following reactivation of heat recovery
function
0
250
Min
rC 7
Recovery function disabling setting
Condensing pressure/temperature level for disabling heat recovery function
If the condensing pressure exceeds the rC07 level the heat recovery function
is automatically disabled.
-50.0
-58
0.0
0
110
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
Int
rC 8
Recovery function enabling differential
Heat recovery function is reactivated if the condensing pressure/temperature
drops below the rC07 rC08 level
0.1
1
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
Int
rC 9
Maximum condensation pressure / temperature recovery disabling time
After expiration of the rC09 delay the heat recovery function is reactivated
regardless the condensing pressure/temperature level.
0
250
Min
rC 10
Condensation ventilation operation in recovery mode
0 = enabled
1 = not enabled
0
1
rC 11
Minimum recovery setting
Defines the minimum limit for the working set-point in heat recovery mode
-50.0
-58
rC12
°C
°F
Dec
Int
rC 12
Maximum recovery setting
Defines the maximum limit for the working set-point in heat recovery mode
rC11
110
230
°C
°F
Dec
Int
rC 13
Recovery set point
Defines the working set-point for heat recovery function (active only in cooling
mode)
rC11
rC12
°C/°F
Dec / int
rC 14
Recovery differential
Defines the working set-point for heat recovery function
0.1
0
25.0
45
°C
°F
Dec
Int
rC 15
Defines the temperature control probe of the machine in recovery mode
0 = condenser water common inlet
1 = circuit 1 condenser water input NTC
2 = circuit 2 condenser water input NTC
3 = circuit 3 condenser water input NTC
4 = circuit 4 condenser water input NTC
5 = circuit 1 condenser water output NTC
6 = circuit 2 condenser water output NTC
7 = circuit 3 condenser water output NTC
8 = circuit 4 condenser water output NTC
9 = condenser water common output NTC
0
9
Function for production of domestic hot water
Parameter
Description
min
max
um
Resolution
FS 1
Activation of domestic hot water production
0 = Disabled
1 = with common return User and domestic hot water heat exchanger
and water piping are physically the same
2 = with dedicated return User and domestic hot water heat exchanger
and water piping are physically separated
0
2
FS 2
Operation priorities
0 = domestic water
1 = heating / cooling
0
1
FS 3
Domestic water set point.
Defines the working set point for the production of domestic hot water.
FS05
FS06
°C
°F
dec
int
FS 4
Domestic water regulation steps intervention band
0.1
1
25.0
45
°C
°F
dec
int
FS 5
Minimum domestic water set point value.
Minimum limit for the domestic water set point
-50.0
-58
FS06
°C
°F
dec
int
FS 6
Maximum domestic water set point value.
Maximum limit for the domestic water set point
FS05
110
230
°C
°F
dec
int
FS 7
Activation of the steps to reach the domestic water set point
0 = activates all the compressors
1 = activates the compressors and heaters
0
1
FS 8
Connection of the domestic water temperature control heaters
0 = no
1 = yes
0
1