1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx iProCHILL 137/205
Recovery function
0 = Disabled
1 = separate hydraulic circuits
2 = hydraulic circuits in parallel
3 = total recovery gas side
Choice of recovery function priority
0 = user side
1 = recovery side
Forced step deactivation time
Forced step deactivation time after rotation of recovery valve
Minimum operation time in recovery mode
Minimum activation time of heat recovery function once enabled
Minimum delay between recovery end and next recovery
Minimum time between disabling and following reactivation of heat recovery
function
Recovery function disabling setting
Condensing pressure/temperature level for disabling heat recovery function
If the condensing pressure exceeds the rC07 level the heat recovery function
is automatically disabled.
Recovery function enabling differential
Heat recovery function is reactivated if the condensing pressure/temperature
drops below the rC07 – rC08 level
Maximum condensation pressure / temperature recovery disabling time
After expiration of the rC09 delay the heat recovery function is reactivated
regardless the condensing pressure/temperature level.
Condensation ventilation operation in recovery mode
0 = enabled
1 = not enabled
Minimum recovery setting
Defines the minimum limit for the working set-point in heat recovery mode
Maximum recovery setting
Defines the maximum limit for the working set-point in heat recovery mode
Recovery set point
Defines the working set-point for heat recovery function (active only in cooling
mode)
Recovery differential
Defines the working set-point for heat recovery function
Defines the temperature control probe of the machine in recovery mode
0 = condenser water common inlet
1 = circuit 1 condenser water input NTC
2 = circuit 2 condenser water input NTC
3 = circuit 3 condenser water input NTC
4 = circuit 4 condenser water input NTC
5 = circuit 1 condenser water output NTC
6 = circuit 2 condenser water output NTC
7 = circuit 3 condenser water output NTC
8 = circuit 4 condenser water output NTC
9 = condenser water common output NTC
Function for production of domestic hot water
Activation of domestic hot water production
0 = Disabled
1 = with common return – User and domestic hot water heat exchanger
and water piping are physically the same
2 = with dedicated return – User and domestic hot water heat exchanger
and water piping are physically separated
Operation priorities
0 = domestic water
1 = heating / cooling
Domestic water set point.
Defines the working set point for the production of domestic hot water.
Domestic water regulation steps intervention band
Minimum domestic water set point value.
Minimum limit for the domestic water set point
Maximum domestic water set point value.
Maximum limit for the domestic water set point
Activation of the steps to reach the domestic water set point
0 = activates all the compressors
1 = activates the compressors and heaters
Connection of the domestic water temperature control heaters
0 = no
1 = yes