1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx iProCHILL 181/205
10.14 SUPPLY FAN OVERLOAD ALARM
Alarm code
AtSF (Supply fan overload alarm)
Display in keyboard
Overl supply fan
Cause of activation
If CF01 = 0 (air/air unit), with DI Evaporator main pump / Supply fan Overload
(DI type=56) active.
On fan start-up, the alarm is ignored for time AL16
Reset
DI not active
Reset
Always manual
Icon
flashing
Action
Alarm relay + buzzer activated
Regulators
Alarm
Relay + buzzer activated
Reverse valve
it follows its regulation
Recovery valve
it follows its regulation
Free-cooling on/off valve
it follows its regulation
Auxiliary relay
it follows its regulation
Idle running valve
it follows its regulation
Supply ventilation
off
Condensation ventilation
off
Support/boiler/anti-freeze
off
Evaporator and condenser
water pump
off
Compressors
off
Pump down solenoid valve
off
10.15 DOMESTIC HOT WATER PUMP FLOW SWITCH ALARM
Alarm code
AHFL (domestic hot water pump flow switch alarm)
Display in keyboard
Sanitary water flow AL
Cause of activation
(the flow switch alarm is only active with FS01 ≠ 0)
Check DI configured as Sanitary water flow switch (DI type=5).
If polarity check not required (AL20=1), after domestic hot water pump active
for AL16 time, if DI active for AL18 time, alarm occur.
If polarity check required (AL201), after domestic hot water pump active for
AL16 time, if DI still keeps the same status as that when domestic hot water
pump is not working for AL18 time, alarm occur.
Reset
DI not active for the time AL19
Reset
Automatic it becomes manual if this alarm active for time AL17 (reset
procedure in functions menu)
Icon
flashing
Action
Alarm (DO type=164) + buzzer relays only activated if the flow switch alarm is
activated in normal working phase
Regulators
Alarm
Relay + buzzer only activated if the flow switch alarm is activated in normal
working phase
Domestic hot water pump
Off when the alarm becomes with manual reset
Production of domestic hot
water function
Off
Other loads
They follow their regulation