1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx iProCHILL 182/205
10.16 SOLAR PANELS WATER PUMP FLOW SWITCH ALARM
APFL (solar panels pump flow switch alarm)
(the flow switch alarm is only active with FS01 ≠ 0)
Check DI configured as Solar panels flow switch (DI type=112).
If polarity check not required (AL20=1), after solar panel pump active for AL16
time, if DI active for AL18 time, alarm occur.
If polarity check required (AL20≠1), after domestic hot water pump active for
AL16 time, if DI still keeps the same status as that when solar panel pump is
not working for AL18 time, alarm occur.
DI not active for the time AL19
Automatic – it becomes manual if this alarm active for time AL17 (reset
procedure in functions menu)
Alarm (DO type=165) + buzzer relays only activated if the flow switch alarm is
activated in normal working phase
Relay + buzzer only activated if the flow switch alarm is activated in normal
working phase
Off when the alarm becomes with manual reset
They follow their regulation
10.17 COMPRESSOR OVERLOAD ALARM
C1tr (compressor n° 1 overload alarm) -…C16tr (compressor n° 16 overload
alarm)
The alarm is detected after AL27 delay from compressor switch-on. If AL30=1,
the detection also enabled when compressor is off.
With DI configured as Compressor 1…16 thermal overload (DI type=34…49)
active, alarm occur.
Always manual. If more than AL28 compressor interventions occur per hour,
password is request to do reset operation. The password is set in par AL31.
Alarm relay (DO type=168…183) + buzzer activated
it follows its regulation
it follows its regulation
Free-cooling on/off valve
it follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
Support/boiler/anti-freeze
It follows/they follow its/their regulation
Pump/and water evaporator
and condenser
It follows its regulation