1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx iProCHILL 183/205
If Par. AL29 = 0 following their regulation
If Par. AL29 = 1 off
It switches-off if there is only 1 compressor per circuit, otherwise it follows its
regulation
10.18 COMPRESSOR HIGH DISCHARGE TEMPERATURE ALARM FROM ANALOGUE INPUT
C1dt…C16dt (compressor n° 1…16 high discharge temperature alarm)
Hi Disch temp.C1…Hi Disch temp.C16
The temperature measured by the probe configured as Compressor 1…16
PTC discharge temperature probe (AI type=1…16) >= AL50 set
The temperature measured by the probe configured as Compressor 1…16
PTC discharge temperature probe (AI type=1…16) <= AL50 set – AL51
differential
Automatic - Manual. If more than AL52 interventions per hour occur. Enter the
functions menu to reset the alarm
Alarm relay (DO type=1)+ buzzer activated
it follows its regulation
it follows its regulation
Free-cooling on/off valve
it follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
Support/boiler/anti-freeze
It follows/they follow its/their regulation
Pump/and water evaporator
and condenser
It follows its regulation
It follows its regulation
It switches-off if there is only 1 compressor per circuit, otherwise it follows its
regulation
Liquid injection solenoid
valve
Off with compressor in OFF