1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx iProCHILL 184/205
10.19 EVAPORATOR WATER INLET HIGH TEMPERATURE ALARM
Alarm code
AEht (evaporator water inlet high temperature alarm)
Display in keyboard
Hi temp.evap.water inlet
Cause of activation
The alarm only detect when CF01>0 (not in air/air unit) and unit is working in
chiller mode.
After compressors start-up for AL61 time, detect the probe selected by AL64. If
the temperature measured by this probe >= AL62 set, alarm occur.
Reset
The temperature measured by the probe configured in AL64 < AL62 set
AL63 differential
Reset
Automatic - Manual
Reset is always manual if AL60 = 0
Reset is always automatic if AL60 = 60
Reset passes from automatic to manual if AL60 goes from 1 to 59
Icon
flashing
Action
Alarm relay + buzzer activated
Regulators
Alarm
Relay + buzzer activated
Compressors
Off
Other loads
It follows its regulation
WARNING:
The alarm only appears if the unit is running with compressor on after time AL61.
The alarm remains in stand-by, OFF remote or with compressor off due to temperature control only if it was
present before and with MANUAL reset.