10.19 EVAPORATOR WATER INLET HIGH TEMPERATURE ALARM
AEht (evaporator water inlet high temperature alarm)
The alarm only detect when CF01>0 (not in air/air unit) and unit is working in
chiller mode.
After compressors start-up for AL61 time, detect the probe selected by AL64. If
the temperature measured by this probe >= AL62 set, alarm occur.
The temperature measured by the probe configured in AL64 < AL62 set –
AL63 differential
Automatic - Manual
Reset is always manual if AL60 = 0
Reset is always automatic if AL60 = 60
Reset passes from automatic to manual if AL60 goes from 1 to 59
Alarm relay + buzzer activated
It follows its regulation
WARNING:
The alarm only appears if the unit is running with compressor on after time AL61.
The alarm remains in stand-by, OFF remote or with compressor off due to temperature control only if it was
present before and with MANUAL reset.