1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx iProCHILL 186/205
It follows its regulation
It follows its regulation
Support/boiler/anti-freeze
It follows its regulation
Pump/and water evaporator
and condenser
It follows its regulation
It follows its regulation
It follows its regulation
10.22 UNLOADING ALARM DUE TO HIGH CONDENSATION TEMPERATURE/PRESSURE IN
COOLING WORKING MODE
(Not available)
b1Cu…b4Cu (circuit n° 1…4 unloading condenser high temperature/pressure
alarm)
Unload high t/p circ1…Unload high t/p circ4
When working, if the probe configured as condensation temperature or
pressure control measures a value > Un11 set
of the condensation pressure or temperature measures a value < Un11–
Un12 differential
By unloading function inserted after the time set Par. Un15
Alarm relay + buzzer NOT activated
Relay + buzzer NOT activated
It follows its regulation
it follows its regulation
Free-cooling on/off valve
it follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
Support/boiler/anti-freeze
It follows its regulation
Pump/and water evaporator
and condenser
It follows its regulation
It follows its regulation
It follows its regulation