10.23 HEAT RECOVERY DISABLING SIGNAL DUE TO HIGH CONDENSATION
TEMPERATURE/PRESSURE IN COOLING WORKING MODE
b1rC…b4rC (circuit n° 1…4 recovery disabling alarm)
Recovery dis.hi t/p C1…Recovery dis.hi t/p C4
RC01=3, if the probe for disable heat recovery (configured as condensation
temperature or pressure) measures a value >= rC07 set, alarm occur.
The condensation pressure or temperature probe measures a value <=
rc07 set – rC08 differential
Heat recovery disabling function is intervened due to Par. rC09 time
expired.
Alarm relay + buzzer NOT activated
Relay + buzzer NOT activated
It follows its regulation
Free-cooling on/off valve
it follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
Support/boiler/anti-freeze
It follows its regulation
Pump/and water evaporator
and condenser
It follows its regulation
It follows its regulation
It follows its regulation
10.24 UNLOADING SIGNAL DUE TO LOW EVAPORATION PRESSURE IN HEATING WORKING MODE
(Not available)
b1Eu (circuit n° 1 unloading from condenser coil signal)
b2Eu (circuit n° 2 unloading from condenser coil signal)
b3Eu (circuit n° 3 unloading from condenser coil signal)
b4Eu (circuit n° 4 unloading from condenser coil signal)
Unload lo press.circ1…Unload lo press.circ4
When working, if the probe configured as condensation temperature,
configured as pressure control or as evaporation pressure, measures a value <
Un13 set
if the condensation pressure/temperature or the evaporation pressure
measures a value > Un13 + Un14
With unloading function inserted after the time set Par. Un15
Alarm relay + buzzer NOT activated
Relay + buzzer NOT activated
It follows its regulation
it follows its regulation
Free-cooling on/off valve
it follows its regulation
It follows its regulation
It follows its regulation