10.26 PUMP DOWN ALARM WITH LOW PRESSURE PRESSURE SWITCH/TRANSDUCER IN
STOPPING
b1PH…b4PH (pump-down alarm in circuit n° 1…4 in stopping)
Pump down at stop circ1…Pump down at stop circ4
With Pd1 ≠ 0, pump-down when compressor stopping:
Pressure switch DI configured: with DI configured as Circuit 1…4 pump
down pressure switch (DI type = 85-88) or Low pressure switch circuit 1…4
(DI type = 14-17) not active and the pump-down ends by time Pd4.
Transducer configured: the probe configured as Circuit 1…4 evaporating
pressure probe (4÷20 mA / 0÷ 5 Volt) (AI type = 56-59) measures the
value >= set Pd02 + Pd03 differential and the pump-down ends by time
Pd04.
The circuit has compressor running. User push RESET key from the keyboard.
Alarm relay + buzzer activated only when the alarm becomes manual reset
Relay + buzzer activated only when the alarm becomes manual reset
It follows its regulation
it follows its regulation
Free-cooling on/off valve
it follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
Support/boiler/anti-freeze
It follows its regulation
Pump/and water evaporator
and condenser
It follows its regulation
Off with manual reset alarm
It follows its regulation
10.27 PUMP DOWN ALARM WITH LOW PRESSURE TRANSDUCER IN START-UP
b1PL…b4PL (pump-down alarm in circuit n° 1…4 in start-up)
Pump down at start circ1…Pump down at start circ4
With Pd1 ≠ 0, pump-down when compressor start-up:
Pressure switch DI configured: with DI configured as Circuit 1…4
pump down pressure switch (DI type = 85-88) or Low pressure switch
circuit 1…4 (DI type = 14-17) keeps active and the pump-down ends by
time Pd4.
Transducer configured: the probe configured as Circuit 1…4
evaporating pressure probe (4÷20 mA / 0÷ 5 Volt) (AI type = 56-59)
measures the value <= set Pd02 and the pump-down ends by time Pd04.
DI deactivate or probe value > set Pd02
Automatic/becomes manual after Pd8 interventions per hour if Pd9 =1 (reset
procedure in functions menu) If Pd9 = 0 it remains with automatic reset. It is
recorded in the historical alarms only with manual reset
Alarm relay + buzzer activated only when the alarm becomes manual reset
Relay + buzzer activated only when the alarm becomes manual reset