1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx iProCHILL 190/205
Reverse valve
It follows its regulation
Recovery valve
it follows its regulation
Free-cooling on/off valve
it follows its regulation
Auxiliary relay
It follows its regulation
Idle running valve
It follows its regulation
Supply ventilation
It follows its regulation
Condensation ventilation
It follows its regulation
Support/boiler/anti-freeze
It follows its regulation
Pump/and water evaporator
and condenser
It follows its regulation
Compressors
Off with manual reset alarm
Pump down solenoid valve
It follows its regulation
10.28 EVAPORATOR WATER PUMP OVERLOAD ALARM
Alarm code
AtE1 (evaporator n° 1 water pump overload alarm)
AtE2 (evaporator support n° 2 water pump overload alarm)
Display in keyboard
Evap.pump 1 overl
Evap.pump 2 overl
Cause of activation
DI configured as Evaporator main pump / Supply fan Overload (DI type=56)
active and par CF010.
DI configured as Evaporator support pump Overload (DI type=57) active.
Reset
With DI not active
Reset
Manual. (reset procedure in functions menu)
Icon
flashing
Action
Alarm relay (DO type=1)+ buzzer activated
Regulators
Alarm
Relay + buzzer activated
Reverse valve
It follows its regulation
Recovery valve
it follows its regulation
Free-cooling on/off valve
it follows its regulation
Auxiliary relay
it follows its regulation
Idle running valve
It follows its regulation
Supply ventilation
Off if no pump is available
Condensation ventilation
Off if no pump is available
Support/boiler/anti-freeze
It follows its regulation
Evaporator water pump
Off if pump is available
Condenser water pump
It follows its regulation
Compressors
Off if pump is available
Pump down solenoid valve
Off if pump is available