10.31 GENERIC ALARM 2
DI configured as Generic alarm 2 digital input (DI type=90) active for the time
set in the Par AL58
DI configured as Generic alarm 2 digital input (DI type=90) not active for the
time set in the Par AL59
If AL56=0, always automatic.
If AL56=1, automatic-manual. It becomes manual after AL57
interventions/hour.
Alarm relay (DO type=167) + buzzer activated
10.32 COMPRESSORS MAINTENANCE ALARM
C1Mn …C16Mn (compresser n° 1…16 maintenance request)
C1 maint req. …C16 maint req.
Compressor is configured and its working hours > timer set by CO53
Reset working hours (from keyboard)
Automatic (after the hours reset)
Alarm relay + buzzer activated
Relay(DO type=1) + buzzer activated
They follow their regulation
10.33 EVAPORATOR FAN/ PUMPS MAINTENANCE ALARM
AEP1 (evaporator n° 1 water pump maintenance request)
AEP2 (evaporator support n° 2 water pump maintenance request)
Evap.pump 1 maint
Evap.pump 2 maint
Water/fan pump working hours >= timer set PA13
Water support pump working hours >= timer set PA14
Reset working hours (From keyboard)
Automatic (after the hours reset)
Alarm relay (DO type=1) + buzzer activated
They follow their regulation