1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx iProCHILL 192/205
10.31 GENERIC ALARM 2
Alarm code
ALc2 (Generic alarm 2)
Display in keyboard
Generic AL2
Cause of activation
DI configured as Generic alarm 2 digital input (DI type=90) active for the time
set in the Par AL58
Reset
DI configured as Generic alarm 2 digital input (DI type=90) not active for the
time set in the Par AL59
Reset
If AL56=0, always automatic.
If AL56=1, automatic-manual. It becomes manual after AL57
interventions/hour.
Icon
flashing
Action
Alarm relay (DO type=167) + buzzer activated
Regulators
Alarm
Relay + buzzer activated
Other loads
Off
10.32 COMPRESSORS MAINTENANCE ALARM
Alarm code
C1Mn C16Mn (compresser n° 1…16 maintenance request)
Display in keyboard
C1 maint req. C16 maint req.
Cause of activation
Compressor is configured and its working hours > timer set by CO53
Reset
Reset working hours (from keyboard)
Reset
Automatic (after the hours reset)
Icon
flashing
Action
Alarm relay + buzzer activated
Regulators
Alarm
Relay(DO type=1) + buzzer activated
Other loads
They follow their regulation
10.33 EVAPORATOR FAN/ PUMPS MAINTENANCE ALARM
Alarm code
AEP1 (evaporator n° 1 water pump maintenance request)
AEP2 (evaporator support n° 2 water pump maintenance request)
Display in keyboard
Evap.pump 1 maint
Evap.pump 2 maint
Cause of activation
Water/fan pump working hours >= timer set PA13
Water support pump working hours >= timer set PA14
Reset
Reset working hours (From keyboard)
Reset
Automatic (after the hours reset)
Icon
flashing
Action
Alarm relay (DO type=1) + buzzer activated
Regulators
Alarm
Relay + buzzer activated
Other loads
They follow their regulation