10.34 CONDENSER PUMPS MAINTENANCE ALARM
ACP1 (condenser n° 1 water pump maintenance request)
ACP2 (condenser n° 2 water pump maintenance request)
Cond.pump 1 maint
Cond.pump 2 maint
Condenser water pump 1 working hours >= timer set PA29
Condenser water pump 2 working hours >= timer set PA30
Reset working hours (in functions menu)
Automatic (after the hours reset)
Alarm relay (DO type=1) + buzzer activated
They follow their regulation
10.35 POWER SUPPLY FREQUENCY ALARM
AFr (power supply frequency alarm)
If relay Circuit 1 ON/OFF Fan 2nd step (DO type=15) and Circuit 1 ON/OFF
Fan 3rdstep (DO type=16) all not configured, this alarm will never occur.
Otherwise, if SP13≠ 2 and power supply frequency is different from that
configured in the Par SP13, alarm occurs.
SP13 = 2, frequency control disabled.
Or power supply frequency is the same as that configured in the Par SP13.
Alarm relay (DO type=1) + buzzer activated
10.36 XEV20D NOT CONNECT ALARM
AET1 …AET4 (XEV20D 1... XEV20D 4 not connect alarm)
AET1: Et09+Et10>0, XEV20D 1 lose communication by can bus.
AET2: Et11+Et12>0, XEV20D 2 lose communication by can bus.
AET3: Et13+Et14>0, XEV20D 3 lose communication by can bus.
AET4: Et15+Et16>0, XEV20D 4 lose communication by can bus.
Et09...Et16=0 or XEV20D communication is recovered.
Alarm relay (DO type=1) + buzzer activated