1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx iProCHILL 194/205
10.37 EXPANSION MOUDLE NOT CONNECT ALARM
AEM1 …AEM4 (IPROEX60D 1... IPROEX60D 4 not connect alarm)
The expansion IPROEX60D IO (AI/DI/AO/DO) is used and lose communication
by can bus.
IPROEX60D IO is disabled or communication is recovered.
Alarm relay (DO type=1) + buzzer activated
10.38 PHASES SEQUENCE ALARM
APS (Phases sequence alarm)
Digital input Phase sequence relay (DI type=113) active.
Digital input Phase sequence relay deactivate.
Alarm relay (DO type=153) + buzzer activated
10.39 ANTI-FREEZE ALARM IN FREE-COOLING
AFFC (Anti-freeze alarm in free-cooling)
FC01 = 4, During free-cooling working if External air temperature NTC
temperature probe (free-cooling) (AI type=34) value <= set FC07 for FC24
times. AFFC alarm will be signal after a delay of AL67.
External air temperature >= set FC07 + differential FC08.
Automatic – becomes manual after AL68 interventions/hour.
Alarm relay (DO type=1) + buzzer activated