1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx iProCHILL 195/205
10.40 BOILER OVERLOAD ALARM
Atrb (Boiler overload alarm)
Digital input Thermal heaters (DI type=114) active.
Digital input Thermal heaters deactivate.
Automatic – becomes manual after AL70 interventions/hour.
Alarm relay (DO type=1) + buzzer activated
If AH01=1, compressor working should affected by auxiliary heating request.
But when this Atrb alarm occur and AL69=1, compressor will not be affected.
10.41 BOILER LOCK ALARM
Digital input Block heaters (DI type=115) active.
Digital input Block heaters deactivate.
Automatic – becomes manual after AL71 interventions/hour.
Alarm relay (DO type=1) + buzzer activated
If AH01=1, compressor working should affected by auxiliary heating request.
But when this Atrb alarm occur and AL69=1, compressor will not be affected.