If a digital input is configured as Digital input working in RTC automatic enabling (time band)/manual
(keyboard) mode (DI type=91) and is active, the working via the internal clock is disabled. Otherwise, if this
digital input is not configured or configured but not active, enables the working via the internal clock.
The unit is forced to switch off within the time band.
Set the time band with Par ES01-ES06, and select weekly time band by Par ES18-ES24. If current time is
inside the setting band, the unit will be shut off automatically, and the keyboard shows Unit OFF through
clock.
The RTC time band also can be configured from keyboard.
Enter into the TIME/TIME PERIOD screen from SERVICE menu.
Enable the Auto Power Off option, set Time band N1/N3 in page 2.