EasyManua.ls Logo

Emerson Dixell iProChill IPC115D - Page 21

Emerson Dixell iProChill IPC115D
205 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx iProCHILL 21/205
Select time band from Monday to Sunday in the next pages last column Auto On-Off.
5.2.2 Working With “Ventilation Only” Digital Input (Air-Air Unit Only)
If the unit has been configured as AIR-AIR, during clock off, it is possible to decide whether to enable
ventilation or not. When ventilation enabled, the screen will be:
This working mode is only enabled if the clock is present and enabled.
Set CF01=0, select air/air unit.
Set ES01-06, ES18-24 to enable the function automatic shutdown by RTC.
If a digital input is configured as Digital input working with supply fan only (DI type=92) and is active,
when current time is inside the automatic shutdown time band, the unit will work in Ventilation only mode.
In Ventilation only mode, only relay configured as supply fan is enabled.
After current time goes out of the automatic shutdown time band, the unit will back to normal working mode.
WARNING: In ventilation only mode, the supply fan will forced to active if unit is on. When the unit is placed
in remote off or stand-by, supply fan will switch off after the delay time set in par PA03.
5.2.3 Working With Unit In OFF From RTC If ON Is Forced From Key
ES25
Unit maximum working time in OFF from RTC if forced in ON from key
0
250
Min
10 Min
When the unit is OFF by RTC, user can use keyboard or digital input to force the unit ON. However, the ON
time cant be longer than the time set by Par ES25. After ES25 time, the unit will be forced back to OFF
status.
During ES25 time, user can manually switch OFF the unit by keyboard or digital input.

Related product manuals