13.2 CIRCUIT “B” OUTPUTS ALARM BLOCK TABLE
Code
Alarm
Alarm description
Compressors
Circuit (n)
Condensation
Ventilation Circuit (n)
b(n)HP
Circuit high pressure pressure switch(n)
Yes
Yes after 60 secs.
b(n)LP
Circuit low pressure pressure switch(n)
Yes
Yes
b(n)AC
Anti-freeze in cooling circuit (n)
Yes
Yes
b(n)AH
Anti-freeze in heating circuit (n)
Yes
Yes
b(n)A
Low temperature/anti-freeze alarm in circuit (n)
Yes
Yes
b(n)hP
Condensation high pressure transducer circuit(n)
Yes
Yes after 60 secs.
b(n)lP
Circuit (n) low condensation/evaporator temperature
NTC probe
Yes
Yes
b(n)tF
Circuit ventilation circuit breaker alarm (n)
Yes
Yes
b(n)dF
Circuit defrost alarm signal(n)
b(n)Cu
Unloading signal due to circuit (n) condensation temp.
press.
b(n)Eu
Unloading signal due to circuit (n) evaporator low temp.
b(n)rC
Circuit (n) heat recovery disabling signal
b(n)PH
Circuit pump down stopping alarm (n)
Yes
Yes
b(n)PL
Circuit pump down start-up alarm (n)
Yes
Yes
Where the letter (n) identifies the circuit n° 1 or circuit n° 2
13.3 COMPRESSOR "C" ALARMS OUTPUTS BLOCK TABLE
Code
Alarm
Alarm description
Compressor
(n)
Circuit compressors not
affected
C(n)HP
Compressor high pressure pressure switch(n)
Yes
C(n)oP
Compressor (n) pressure switch/oil float
Yes
C(n)tr
Compressor circuit breaker alarm (n) with AL47
= 0 - 1
Yes
C(n)tr
Compressor circuit breaker alarm (n) with AL47
from 0
Yes
Yes
C(n)dt
Compressor high discharge temperature
Yes
C(n)Mn
Compressor maintenance (n)
Where the letter (n) identifies the compressor n° 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16