1592023130 XM670K_XM679K GB r4.2 26.06.2017.docx XM670K - XM679K 9/10
SFd
0.3
Pr1
Start function duration
0 ÷ 42.0(252) (min.10sec)
OPd
85
Pr1
Opening percentage after defrost
phase
0 ÷ 100
Pdd
0.3
Pr1
Post defrost function duration
0 ÷ 42.0(252) (min.10sec)
MnF
100
Pr1
Maximum opening percentage at
normale functioning
0 ÷ 100
dCL
0
Pr1
Delay before stopping valve
regulation
0 ÷ 255 s
Fot
nu
Pr1
Forced opening percentage
0 ÷ 100 - "nu"(101)
PA4
-0.5
Pr2
Probe value at 4 mA or at 0V
BAR : [PrM=rEL] -1.0 ÷ P20
[PRM=Abs] 0.0 ÷ P20
PSI : [PrM=rEL] -14 ÷ P20
[PRM=Abs] 0 ÷ P20
dKP : [PrM=rEL] -10 ÷ P20
[PRM=Abs] 0 ÷ P20
P20
11.0
Pr2
Probe value at 20 mA or at 5V
BAR : [PrM=rEL] PA4 ÷ 50.0
[PrM=AbS] PA4 ÷ 50.0
PSI : [PrM=rEL] PA4 ÷ 725
[PrM=AbS] PA4 ÷ 725
dKP : [PrM=rEL] PA4 ÷ 500
[PrM=AbS] PA4 ÷ 500
LPL
-0.5
Pr1
Lower pressure limit for superheat
regulation
PA4 ÷ P20
MOP
11.0
Pr1
Maximum operating pressure
threshold
LOP ÷ P20
LOP
-0.5
Pr1
Lowest operating pressure
threshold
PA4 ÷ MOP
dML
30
Pr1
Delta MOP-LOP opening variation
0 ÷ 100
MSH
80.0
Pr1
Maximum superheat alarm
threshold
[LSH ÷ 80,0°C] [LSH ÷ 144°F]
LSH
2.0
Pr1
Minimum superheat alarm
threshold
[0.0 ÷ MSH °C] [0 ÷ MSH °F]
SHy
2.0
Pr2
Superheat alarm hysteresis
[0.1°C ÷ 25.5°C] [1°F ÷ 45°F]
SHd
3.0
Pr1
Superheat alarm activation delay
0 ÷ 42.0(252) (min.10sec)
FrC
100
Pr1
Fast-recovery costant
0 ÷ 100
SUb
10
Pr2
Pressure filter
0÷100
SLb
5
Pr2
Reaction time
0÷255s
Defrost
dPA
P2
Pr1
Defrost probe A
nP(0) - P1(1) - P2(2) - P3(3) -
P4(4) - P5(5)
dPb
nP
Pr1
Defrost probe B
nP(0) - P1(1) - P2(2) - P3(3) -
P4(4) - P5(5)
dPE
100
Pr1
Virtual probe percentage (defrost
temperature)
0 ÷ 100 (100=dPA, 0=dPb)
tdF
EL
Pr1
Defrost type
EL(0) - in(0)
EdF
in
Pr1
Defrost mode: Clock or interval
rtc(0) - in(1)
Srt
150
Pr1
Heater set point during defrost
[-55.0°C ÷ 150°C] [-67°F ÷
302°F]
Hyr
2.0
Pr1
Differential for heater
[0.1°C ÷ 25.5°C] [1°F ÷ 45°F]
tod
255
Pr1
Time out for heater
0 ÷ 255 (min.)
dtP
0.1
Pr1
Minimum temperature difference
to start defrost
[0.1°C ÷ 50.0°C] [1°F ÷ 90°F]
ddP
60
Pr1
Delay before starting defrost
0 ÷ 60 (min.)
d2P
n
Pr1
Defrost with two probes
n(0) Y(1)
dtE
8.0
Pr1
Defrost termination temperature
(Probe A)
[-55.0°C ÷ 50.0°C] [-67°F ÷
122°F]
dtS
8.0
Pr1
Defrost termination temperature
(Probe B)
[-55.0°C ÷ 50.0°C] [-67°F ÷
122°F]
idF
6
Pr1
Interval between defrosts
0 ÷ 120 (hours)
MdF
30
Pr1
Defrost Maximum duration
0 ÷ 255 (min.)
dSd
0
Pr1
Start defrost delay
0 ÷ 255 (min.)
dFd
it
Pr1
Display during defrost
rt(0) - it(1) - SEt(2) - dEF(3)
dAd
30
Pr1
Defrost display time out
0 ÷ 255 (min.)
Fdt
0
Pr1
Drain down time
0 ÷ 255 (min.)
dPo
n
Pr1
Defrost at start-up
n(0) Y(1)
dAF
0.0
Pr1
Defrost delay after continuous
cycle
0 ÷ 24.0(144) (hours.10min)
Fan
FPA
P2
Pr1
Fan probe A
nP(0) - P1(1) - P2(2) - P3(3) -
P4(4) - P5(5)
FPb
nP
Pr1
Fan probe B
nP(0) - P1(1) - P2(2) - P3(3) -
P4(4) - P5(5)
FPE
100
Pr1
Virtual probe percentage (fan
management)
0 ÷ 100 (100=FPA, 0=FPb)
FnC
O-n
Pr1
Fan operating mode
C-n(0) - O-n(1) - C-y(2) - O-y(3)
Fnd
10
Pr1
Fan delay after defrost
0 ÷ 255 (min.)
FCt
10
Pr1
Temperature differential to avoid
short cycles of fans
[0.0°C ÷ 50.0°C] [0°F ÷ 90°F]
FSt
2.0
Pr1
Fan stop temperature
[-55.0°C ÷ 50.0°C] [-67°F ÷
122°F]
FHy
1.0
Pr1
Fan stop differential
[0.1°C ÷ 25.5°C] [1°F ÷ 45°F]
Fod
0
Pr1
Fan activation time after defrost
(without compressor)
0 ÷ 255 (min.)
Fon
0
Pr1
Fan ON time
0÷15 (min.)
FoF
0
Pr1
Fan OFF time
0÷15 (min.)
trA
UAL
Pr2
Kind of regulation for modulating
output
UAL(0) - rEG(1) - AC(2)
SOA
80
Pr2
Fixed speed for fan
AMi ÷ AMA
SdP
30.0
Pr2
Default Dew Point value
[-55.0°C ÷ 50.0°C] [-67°F ÷
122°F]
ASr
1.0
Pr2
Differential for fan / offset for anti
sweat heater
[-25.5°C ÷ 25.5°C] [-45°F ÷ 45°F]
PbA
5.0
Pr2
Proportional band for modulating
output
[0.1°C ÷ 25.5°C] [1°F ÷ 45°F]
AMi
0
Pr2
Minimum output for modulating
output
0 ÷ AMA
AMA
100
Pr2
Maximum output for modulating
output
AMi ÷ 100
AMt
3
Pr2
Time with fan at maximum speed
0 ÷ 255 s
Alarm
rAL
P1
Pr1
Probe for temperature alarm
nP(0) - P1(1) - P2(2) - P3(3) -
P4(4) - P5(5) - tEr(6)
ALC
Ab
Pr1
Temperature alarm configuration
rE(0) - Ab(1)
ALU
10
Pr1
High temperature alarm setting
[0.0°C ÷ 50.0°C o ALL ÷ 150.0°]
[0°F ÷ 90°F o ALL ÷ 302°F]
ALL
-30
Pr1
Low temperature alarm setting
[0.0°C ÷ 50.0°C o -55,0°C ÷
ALU] [0°F ÷ 90°F o -67°F ÷
ALU°F]
AHy
1.0
Pr1
Differential for temperature alarm
[0.1°C ÷ 25.5°C] [1°F ÷ 45°F]
ALd
15
Pr1
Temperature alarm delay
0 ÷ 255 (min.)
dLU
150
Pr2
High temperature alarm setting
(defrost probe)
[0.0°C ÷ 50.0°C o dLL ÷ 150.0°]
[0°F ÷ 90°F o dLL ÷ 302°F]
dLL
-55
Pr2
Low temperature alarm setting
(defrost probe)
[0.0°C ÷ 50.0°C o -55,0°C ÷
dLU] [0°F ÷ 90°F o -67°F ÷
dLU°F]
dAH
1.0
Pr2
Differential for temperature alarm
(defrost probe)
[0.1°C ÷ 25.5°C] [1°F ÷ 45°F]
ddA
15
Pr2
Temperature alarm delay (defrost
probe)
0 ÷ 255 (min.)
FLU
150
Pr2
High temperature alarm setting
(fan probe)
[0.0°C ÷ 50.0°C o FLL ÷ 150.0°]
[0°F ÷ 90°F o FLL ÷ 302°F]
FLL
-55
Pr2
Low temperature alarm setting
(fan probe)
[0.0°C ÷ 50.0°C o -55,0°C ÷
FLU] [0°F ÷ 90°F o -67°F ÷
FLU°F]
FAH
1.0
Pr2
Differential for temperature alarm
(fan probe)
[0.1°C ÷ 25.5°C] [1°F ÷ 45°F]
FAd
15
Pr2
Temperature alarm delay (fan
probe)
0 ÷ 255 (min.)
dAo
1.3
Pr1
Delay of temperature alarm at
start-up
0 ÷ 24.0(144) (hours.10min)
EdA
30
Pr1
Alarm delay at the end of defrost
0 ÷ 255 min
dot
15
Pr1
Temperature alarm exclusion after
door open
0 ÷ 255 min
Sti
nu
Pr2
Stop regulation interval
"nu"(0) ÷ 24.0(144)
(hour.10min)
Std
3
Pr2
Stop duration
1 ÷ 255 min
oA6
AUS
Pr2
Sixth relay output configuration
CPr(0) - dEF(1) - FAn(2) - ALr(3)
- LiG(4) - AUS(5) - db(6) -
OnF(7)
CoM
Cur
Pr2
Modulating output configuration
CUr(0) - tEn(1) - PM5(2) -
PM6(3) - oA7(4)
AOP
cL
Pr1
Alarm relay polarity
OP(0) - CL(1)
iAU
n
Pr1
Auxiliary output indipendent from
ON/OFF state
n(0) Y(1)
Digital Inputs
i1P
cL
Pr1
Digital input 1 polarity
OP(0) - CL(1)
i1F
dor
Pr1
Digital input 1 configuration
EAL(0) - bAL(1) - PAL(2) - dor(3)
- dEF(4) - AUS(5) -LiG(6) -
OnF(7) - Htr(8) - FHU(9) -
ES(10) - Hdy(11)
d1d
15
Pr1
Digital input 1 activation delay
0 ÷ 255 (min.)
i2P
cL
Pr1
Digital input 2 polarity
OP(0) - CL(1)
i2F
LiG
Pr1
Digital input 2 configuration
EAL(0) - bAL(1) - PAL(2) - dor(3)
- dEF(4) - AUS(5) -LiG(6) -
OnF(7) - Htr(8) - FHU(9) -
ES(10) - Hdy(11)
d2d
5
Pr1
Digital input 2 activation delay
0 ÷ 255 (min.)
i3P
cL
Pr1
Digital input 3 polarity
OP(0) - CL(1)
i3F
ES
Pr1
Digital input 3 configuration
EAL(0) - bAL(1) - PAL(2) - dor(3)
- dEF(4) - AUS(5) -LiG(6) -
OnF(7) - Htr(8) - FHU(9) -
ES(10) - Hdy(11)
d3d
0
Pr1
Digital input 3 activation delay
0 ÷ 255 (min.)
nPS
15
Pr1
Number of pressure switch
activation before lock
0 ÷ 15
OdC
F-C
Pr1
Compressor and fan status when
open door
no(0) - FAn(1) - CPr(2) - F-C(3)
rrd
30
Pr1
Outputs restart after door open
alarm
0 ÷ 255 (min.)