1592027610 XW60LT-XW60LRT GB r1.0 13.02.2012.doc XW60LT – XW60LRT 1/6
Digital controller for medium-low temperature
refrigeration applications
XW60LT – XW60LRT
1. GENERAL WARNING ........................................................................................................... 1
2. GENERAL DESCRIPTION .................................................................................................... 1
3. CONTROLLING LOADS ....................................................................................................... 1
4. FRONT PANEL COMMANDS ............................................................................................... 1
5. AUTOMATIC KEYBOARD LOCK .......................................................................................... 2
6. MAX & MIN TEMPERATURE MEMORIZATION .................................................................... 2
7. MAIN FUNCTIONS ............................................................................................................... 2
8. PARAMETERS ..................................................................................................................... 2
9. DIGITAL INPUTS .................................................................................................................. 4
10. TTL SERIAL LINE – FOR MONITORING SYSTEMS ............................................................. 4
11. X-REP OUTPUT – OPTIONAL .............................................................................................. 4
12. INSTALLATION AND MOUNTING ......................................................................................... 4
13. ELECTRICAL CONNECTIONS.............................................................................................. 4
14. HOW TO USE THE HOT KEY .............................................................................................. 4
15. ALARM SIGNALS ................................................................................................................. 4
16. TECHNICAL DATA ............................................................................................................... 5
17. CONNECTIONS ................................................................................................................... 5
18. DEFAULT SETTING VALUES ............................................................................................... 5
1. GENERAL WARNING
1.1 PLEASE READ BEFORE USING THIS MANUAL
This manual is part of the product and should be kept near the instrument for easy and quick reference.
The instrument shall not be used for purposes different from those described hereunder. It cannot be
used as a safety device.
Check the application limits before proceeding.
1.2
SAFETY PRECAUTIONS
Check the supply voltage is correct before connecting the instrument.
Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden
temperature changes with high atmospheric humidity to prevent formation of condensation
Warning: disconnect all electrical connections before any kind of maintenance.
Fit the probe where it is not accessible by the End User. The instrument must not be opened.
In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.p.A.” (see
address) with a detailed description of the fault.
Consider the maximum current which can be applied to each relay (see Technical Data).
Ensure that the wires for probes, loads and the power supply are separated and far enough from each
other, without crossing or intertwining.
In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with
inductive loads could be useful.
Dixell Srl reserves the right to change the composition of its products, even without notice, ensuring the
same and unchanged functionality.
2. GENERAL DESCRIPTION
Models XW60LT and XW60LRT, format 38x185mm, are microprocessor based controllers, suitable
for applications on medium or low temperature ventilated refrigerating units. They have 4 relay outputs
to control compressor, fan, defrost, which can be either electrical or reverse cycle (hot gas) and a
fourth configurable output. They could be provided with a Real Time Clock which allows programming
of up to 6 daily defrost cycles, divided into holidays and workdays. A “Day and Nightfunction with
two different set points is fitted for energy saving. They are also provided with up to four NTC or PTC
probe inputs, the first one for temperature control, the second one, to be located onto the evaporator,
to control the defrost termination temperature and to managed the fan. One of the digital inputs can
operate as third temperature probe. The fourth probe is used to signal the condenser temperature
alarm or to display a temperature. NOTE: the fourth probe is available only for XW60LT models.
The HOT KEY output allows to connect the unit, by means of the external module XJ485-CX, to a
network line ModBUS-RTU compatible such as the dIXEL monitoring units of X-WEB family. It
allows to program the controller by means the HOT KEY programming keyboard.
The instrument is fully configurable through special parameters that can be easily programmed
through the keyboard.
3. CONTROLLING LOADS
3.1 COMPRESSOR
The regulation is performed according
to the temperature measured by the
thermostat probe with a positive
differential from the set point: if the
temperature increases and reaches set
point plus differential the compressor is
started and then turned off when the
temperature reaches the set point
value again.
Time
Temper.
Compr.
SET
ON
In case of fault in the thermostat probe the start and stop of the compressor are timed through
parameters Con and CoF.
3.2 DEFROST
Two defrost modes are available through the tdF parameter: defrost through electrical heater (tdF =
EL) and hot gas defrost (tdF = in).
The defrost interval depends on the presence of the RTC (optional). If the RTC is present is controlled
by means of parameter EdF:
- EdF=in: a defrost starts after elapsing the idF time (standard way for controller without RTC).
EdF=rtC: defrosts are scheduled by using a real time clock system, depending on the hours set in
the parameters Ld1..Ld6, during workdays, and in Sd1…Sd6 during holidays.
Other parameters are used to control defrost cycles: its maximum length (MdF) and two defrost
modes: timed or controlled by the evaporator’s probe (P2P).
At the end of defrost dripping time is started, its length is set in the Fdt parameter. With Fdt=0 the
dripping time is disabled.
3.3 CONTROL OF EVAPORATOR FANS
The fan control mode is selected by means of the FnC parameter:
- FnC=C_n: fans will switch ON and OFF with the compressor and not run during defrost;
- FnC=o_n: fans will run even if the compressor is off, and not run during defrost;
- FnC=C_Y: fans will switch ON and OFF with the compressor and run during defrost;
- FnC=o_Y: fans will run continuously also during defrost.
After defrost, there is a timed fan delay allowing for drip time, set by means of the Fnd parameter.
An additional parameter FSt provides the setting of temperature, detected by the evaporator probe,
above which the fans are always OFF. This is used to make sure circulation of air only if his
temperature is lower than set in FSt.
3.3.1 Forced activation of evaporator fans
This function, managed by the FCt parameter, is designed to avoid short cycles of evaporator fans,
which could happen when the controller is switched on or after a defrost (when the room air warms
the evaporator). If the temperature difference between the evaporator and the room probes is higher
than the value set in the FCt parameter the fans are switched on. With FCt=0 this function is
disabled.
3.3.2 Fans cyclic activation with compressor off.
When FnC=C-n or C-Y (fans working in parallel with the compressor), by means of the Fon and FoF
parameters the fans can carry out on and off cycles even if the compressor is switched off. When the
compressor is stopped the fans go on working for the Fon time. With Fon=0 the fans remain always
off, when the compressor is off.
3.4 AUXILIARY OUTPUT CONFIGURATION
The functioning of the auxiliary relay can be set by the oAx parameters according to the kind of
application. In the following paragraph the possible settings are explaided.
3.4.1 Auxiliary thermostat
A possible use is the anti condensing heater, with the possibility of switching it on and off also by
keyboard.
Parameters involved:
- ACH: kind of regulation for the auxiliary relay: Ht: heating; cL: cooling;
- SAA: set point for auxiliary relay;
- SHy: differential for auxiliary relay;
- ArP: probe for auxiliary relay;
- Sdd: auxiliary output off during defrost.
The differential is given by the SHy parameter.
The auxiliary relay can be switched on also by using the AUX button. In this case it remains on till it’s
manually switched off.
NOTE: If oAx=AUS and ArP=nP (no probe for auxiliary output), the AUX relay can be activated only
by pushing the AUX button of the keyboard.
3.4.2 On/off relay – oAx = onF
In this case the relay is activated when the controller is turned on and de-activated when the controller
is turned off.
3.4.3 Neutral zone regulation
With oAx=db the AUX relay can control a heater element to perform a neutral zone action.
- output oAx cut in = SET-HY;
- output oAx cut out = SET.
3.4.4 Second compressor
With oAx=CP2, the AUX relay operates as second compressor: it is activated in parallel with the
relay of the first compressor, with a proper activation delay (set in the AC1 parameter). Both the
compressors are switched off at the same time.
3.4.5 Alarm relay
With oAx=ALr the AUX relay operates as alarm relay. It is activated every time an alarm happens. Its
status depends on the tbA parameter:
- tbA=Y: the relay is silenced by pressing any key;
- tbA=n: the alarm relay remains on until the alarm condition recovers.
3.4.6 Night blind management during energy saving cycles
With oAx=HES the AUX relay operates to manage the night blind: the relay is energised when the
energy saving cycle is activated by digital input, frontal button or RTC (optional).
4. FRONT PANEL COMMANDS
To display target set point; in programming mode it selects a parameter or
confirm an operation.
(DEF) To start a manual defrost.
(UP) To see the max stored temperature; in programming mode it browses the
parameter codes or increases the displayed value.
(DOWN) To see the min stored temperature; in programming mode it browses
the parameter codes or decreases the displayed value.
(OFF) To switch the instrument off, if onF=oFF.
(LiG) To switch the light, if oA3=Lig.
KEY COMBINATIONS:
Question and Answer IconNeed help?

Do you have a question about the Emerson dixell XW60LT and is the answer not in the manual?

Emerson dixell XW60LT Specifications

General IconGeneral
BrandEmerson
Modeldixell XW60LT
CategoryController
LanguageEnglish

Summary

General Warning

Safety Precautions

Crucial safety measures to be followed before operating the controller.

General Description

Controlling Loads

Compressor

Details on how the compressor is regulated based on temperature set points.

Defrost

Explains the two defrost modes (electrical heater and hot gas) and their settings.

Front Panel Commands

Max & Min Temperature Memorization

How to See the Min Temperature

View the lowest recorded temperature.

How to See the Max Temperature

View the highest recorded temperature.

Main Functions

To Set the Current Time and Day (Only With RTC)

Set the current time and day if the Real Time Clock is present.

How to Change the Setpoint

Adjust the target temperature setting.

Parameters

HY Differential

Intervention differential for set point.

LS Minimum Set Point

Sets the minimum value for the set point.

US Maximum Set Point

Sets the maximum value for set point.

Display

Resolution

Allows decimal point display for temperature readings.

Instrument Display

Selects which probe's value is displayed on the instrument.

Defrost

Defrost Mode

Sets defrost mode based on Real Time Clock or interval.

Defrost Type

Specifies defrost method: electrical heater or hot gas.

Interval Between Defrost Cycles

Determines the time interval between two defrost cycles.

Fans

Fans Operating Mode

Configures fan operation relative to compressor and defrost cycles.

Fans Delay After Defrost

Sets time interval between end of defrost and fan start.

Alarms

Probe Selection For Alarm

Selects probes for temperature alarms.

Temperature Alarms Configuration

Configures temperature alarms relative to absolute or set point.

Maximum Temperature Alarm

Sets the upper limit for temperature alarms.

Minimum Temperature Alarm

Sets the lower limit for temperature alarms.

Digital Inputs

First Digital Input Polarity

Sets polarity for the first digital input.

First Digital Input Configuration

Assigns a function to the first digital input.

Installation and Mounting

Electrical Connections

Details on connecting cables to the instrument terminals.

Probe Connection

Guidance on proper mounting and placement of probes.

How to Use the Hot Key

Program a Hot Key From an Instrument (Upload)

Copy controller settings to a Hot Key device.

Program an Instrument by Using a Hot Key (Download)

Load controller settings from a Hot Key device.

Alarm Signals

Message Causes and Outputs

Table listing alarm messages, their causes, and output behavior.

Technical Data

Dimensions and Mounting

Specifications for housing, panel cut-out, and mounting.

Connections

Overview of terminal connections for the XW60LT model.

Default Setting Values

Parameter Table Overview

Lists default values for various controller parameters.