1592027610 XW60LT-XW60LRT GB r1.0 13.02.2012.doc XW60LT – XW60LRT 5/6
Message Cause Outputs
dA Door open Compressor and fans restarts
EA External alarm Output unchanged.
CA Serious external alarm (i1F=bAL) All outputs OFF.
CA Pressure switch alarm (i1F=PAL) All outputs OFF
rtC Real time clock alarm
Alarm output ON; Other outputs unchanged;
Defrosts according to par. idF Set real time clock
has to be set.
rtF Real time clock board failure
Alarm output ON; Other outputs unchanged;
Defrosts according to par. idF. Contact the
service.
15.1 SILENCING BUZZER / ALARM RELAY OUTPUT
- tbA=Y: the buzzer and the relay are is silenced by pressing any key.
- tbA=n: only the buzzer is silenced while the alarm relay is on until the alarm condition
recovers.
15.2 ALARM RECOVERY
Probe alarms P1, P2, P3 and P4 start some seconds after the fault in the related probe; they
automatically stop some seconds after the probe restarts normal operation. Check connections before
replacing the probe.
Temperature alarms HA, LA, HA2 and LA2 automatically stop as soon as the temperature returns to
normal values.
Alarms EA and CA (with i1F=bAL) recover as soon as the digital input is disabled.
Alarm CA (with i1F=PAL) recovers only by switching off and on the instrument.
15.3 OTHER MESSAGES
on Keyboard enabled after automatic lock.
LOC Keyboard automatically locked
Pon Keyboard unlocked.
PoF Keyboard locked
noP
In programming mode: none parameter is present in Pr1
On the display or in dP2, dP3, dP4: the selected probe is nor enabled
16. TECHNICAL DATA
Housing: self extinguishing ABS
Case: facia 38x185 mm; depth [XW60LT: 76mm], [XW60LRT: 40mm]
Mounting: panel mounting in a 150x31 mm panel cut-out with the 2 metal brackets supplied
Protection: IP20
Frontal protection: IP65
Connections: screw terminal block 2.5 mm
2
heat-resistant wiring and 6.3mm Faston
Power supply: 230Vac or. 110Vac or 24Vac 10%
Power absorption: 5VA max
Display: 3 digits, white LED, 14.2 mm high
Inputs: Up to 4 NTC or PTC probes
Digital inputs: 2 free voltage
Relay outputs for XW60LT models: Total current on loads MAX. 20A
Compressor: relay SPST 20(8) A, 250Vac
Light: relay SPST 8 or 16(3) A, 250Vac
Fans: relay SPST 8(3) A, 250Vac
Defrost: relay SPST 8(3) A, 250Vac
Relay outputs for XW60LRT models: Total current on loads MAX. 16A
Compressor: relay SPST 20(8)A, 250Vac
Light: relay SPST 5A, 250Vac
Fans: relay SPST 5A, 250Vac
Defrost: relay SPST 8(3) A, 250Vac
Other output: buzzer
Serial output: TTL standard
Communication protocol: Modbus - RTU
Data storing: on the non-volatile memory (EEPROM)
Internal clock back-up: 24 hours (only for model with RTC)
Kind of action: 1B
Pollution degree: 2
Software class: A
Rated impulsive voltage: 2500V
Over voltage Category: II
Operating temperature: 0 to 60 °C (32 to 140°F)
Storage temperature: -30 to 85°C (-22 to 185°F).
Relative humidity: 20 to 85% (not condensing)
Measuring and regulation range:
NTC probe: -40 to 110°C (-40 to 230°F)
PTC probe: -50 to 150°C (-58 to 302°F)
Resolution: 0.1°C or 1°C or 1°F (selectable)
Accuracy (ambient temp. 25°C): ±0.7°C ±1 digit
17. CONNECTIONS
17.1 XW60LT
Supply: 120Vac or 24Vac: connect to terminals 11-12
The X-REP output is optional
The light relay can be also 16(5)A according to the model
17.2 XW60LRT
18. DEFAULT SETTING VALUES
Label
Name Range °C/°F Level
Set Set point LS to US -5.0 - - -
rtC* Real time clock menu - - Pr1
Hy Differential
[0.1 to 25.5°C]
[1 to 45°F]
2.0 Pr1
LS Minimum set point
[-55°C to SET]
[-67°F to SET]
-50.0 Pr2
US Maximum set point
[SET to 150°C]
[SET to 302°F]
110 Pr2
ot Thermostat probe calibration
[-12 to 12°C]
[-21 to 21°F]
0.0 Pr1
P2P
Evaporator probe presence n=not present; Y=present Y Pr1
oE Evaporator probe calibration
[-12 to 12°C]
[-21 to 21°F]
0.0 Pr2
P3P
Third probe presence n=not present; Y=present n Pr2
o3 Third probe calibration
[-12 to 12°C]
[-21 to 21°F]
0 Pr2
P4P
Fourth probe presence (only for
XW60LT)
n=not present; Y=present n Pr2
o4
Fourth probe calibration (only for
XW60LT)
[-12 to 12°C]
[-21 to 21°F]
0 Pr2
odS
Outputs delay at start up 0 to 255 min 0 Pr2
AC Anti-short cycle delay 0 to 50 min 1 Pr1
Ac1 Second compressor start delay 0 to 255 sec 5 Pr2
rtr P1-P2 percentage for regulation 0 to 100 (100=P1 , 0=P2) 100 Pr2
CCt Continuous cycle duration 0.0 to 24h00min 0.0 Pr2
CCS
Set point for continuous cycle
[-55.0 to 150.0°C]
[-67 to 302°F]
-5 Pr2
Con
Compressor ON time with faulty probe 0 to 255 min 15 Pr2
CoF
Compressor OFF time with faulty probe 0 to 255 min 30 Pr2
CF Temperature measurement unit °C to °F °C Pr2
rES Resolution in=integer; dE= dec.point dE Pr1
Lod
Probe displayed P1; P2 P1 Pr2
rEd
2
X-REP display P1; P2; P3; P4; SEt; dtr P1 Pr2
dLy Display temperature delay 0.0 to 20min00sec (10 sec) 0.0 Pr2
dtr P1-P2 percentage for display 1 to 99 50 Pr2
EdF*
Kind of interval for defrost rtC; in in Pr2
tdF Defrost type EL=el. heater; in= hot gas EL Pr1
dFP
Probe selection for defrost termination nP; P1; P2; P3; P4 P2 Pr2
dtE Defrost termination temperature -50 to 50°C 8 Pr1
idF Interval between defrost cycles 1 to 120 hours 6 Pr1
MdF
(Maximum) length for defrost 0 to 255 min 30 Pr1
dSd
Start defrost delay 0 to 99min 0 Pr2
dFd
Displaying during defrost rt; it; SEt; DEF it Pr2
dAd
MAX display delay after defrost 0 to 255 min 30 Pr2
Fdt Draining time 0 to 120 min 0 Pr2
dPo
First defrost after start-up n=after idF; y=immed. n Pr2
dAF
Defrost delay after fast freezing 0.0 to 23h50min 0.0 Pr2
Fnc Fan operating mode C-n; o-n; C-y; o-Y o-n Pr1
Fnd
Fan delay after defrost 0 to 255 min 10 Pr1
FCt
Differential of temperature for forced
activation of fans
0 yo 50°C 10 Pr2
FSt Fan stop temperature
[-50 to 50°C]
[-55 to 122°F]
2 Pr1
Fon
Fan on time with compressor off 0 to 15 min 0 Pr2
FoF
Fan off time with compressor off 0 to 15 min 0 Pr2
FAP
Probe selection for fan management nP; P1; P2; P3; P4 P2 Pr2
ACH
Kind of action for auxiliary relay CL; Ht cL Pr2
SAA
Set Point for auxiliary relay
[-55.0 to 150°C]
[-67 to 302°F]
0,0 Pr2
SHy
Differential for auxiliary relay
[0.1 to 25.5°C]
[1 to 45°F]
2,0 Pr2
ArP Probe selection for auxiliary relay nP; P1; P2; P3; P4 nP Pr2
Sdd
Auxiliary relay operating during defrost n(0); Y(1) n Pr2
ALP
Alarm probe selection nP; P1; P2; P3; P4 P1 Pr2
ALC
Temperat. alarms configuration
rE= related to set;
Ab = absolute
Ab Pr2
ALU
MAXIMUM temperature alarm
[SET to 150.0°C]
[SET to 302°F]
110,0 Pr1
ALL
Minimum temperature alarm
[-55.0°C to SET]
[-67°F to SET]
-50,0 Pr1
AFH
Differential for temperat. alarm recovery
[0.1 to 25.5°C]
[1 to 45°F]
2,0 Pr2
ALd
Temperature alarm delay 0 to 255 min 15 Pr2
dAo
Delay of temperature alarm at start up 0.0 to 23h50min 1,3 Pr2
AP2
Probe for temperat. alarm of condenser nP; P1; P2; P3; P4 P4 Pr2
AL2
Condenser for low temperat. alarm
[-55 to 150°C]
[-67 to 302°F]
-40 Pr2
AU2
Condenser for high temperat. alarm
[-55 to 150°C]
[-67 to 302°F]
110 Pr2