17. DEFAULT SETTING VALUES
[0.1 to 25.5°C]
[1 to 45°F]
[-100°C to SET]
[-148°F to SET]
[SET to 150°C]
[SET to 302°F]
Thermostat probe calibration
[-12.0 to 12.0°C]
[-21 to 21°F]
Evaporator probe presence
Evaporator probe calibration
[-12.0 to 12.0°C]
[-21 to 21°F]
[-12.0 to 12.0°C]
[-21 to 21°F]
[-12.0 to 12.0°C]
[-21 to 21°F]
Outputs delay at start up
P1-P2 percentage for regulation
Continuous cycle duration
0.0 to 24h00min, res. 10 min
Set point for continuous cycle
[-100 to 150.0°C]
[-148 to 302°F]
Compressor ON time with faulty probe
Compressor OFF time with faulty probe
Temperature measurement unit
Display temperature delay
0.0 to 20min00sec, res. 10 sec
P1-P2 percentage for display
Probe selection for defrost termination
Defrost termination temperature
[-55 to 50.0°C]
[-67 to 122°F]
Interval between defrost cycles
(Maximum) length for defrost
Displaying during defrost
MAX display delay after defrost
First defrost after start-up
Defrost delay after fast freezing
0.0 to 24h00min, res. 10 min
Differential of temperature for forced
activation of fans
[-55 to 50.0°C]
[-67 to 122°F]
Fan on time with compressor off
Fan off time with compressor off
Probe selection for fan management
Temperat. alarms configuration
MAXIMUM temperature alarm
Rel: [0.0 to 50.0°C] [0 to 90°F]
AbS: [ALL to 150°C] [ALL to 302°F]
Minimum temperature alarm
Rel: [0.0 to 50.0°C] [0 to 90°F]
AbS: [-100°C to ALU] [-148°F to ALU]
Differential for temperat. alarm recovery
[0.1 to 25.5°C]
[1 to 45°F]
Delay of temperature alarm at start up
0.0 to 24h00min, res. 10 min
Probe for temperat. alarm of condenser
Condenser for low temperat. alarm
[-100 to 150°C]
[-148 to 302°F]
Condenser for high temperat. alarm
[-100 to 150°C]
[-148 to 302°F]
Differ. for condenser temp. alar.
recovery
[0.1 to 25.5°C]
[1 to 45°F]
Condenser temperature alarm delay
Delay of cond. temper. alarm at start up
0.0 to 24h00min, res. 10 min
Compr. off for condenser low
temperature alarm
Compr. off for condenser high
temperature alarm
Fourth relay configuration
ALr = alarm; dEF = do not select it;
LiG =Light; AUS =AUX; onF=always
on; FAn= do not select it; db = neutral
zone; CP2 = second compressor;
dF2 = do not select it
Alarm relay polarity (oA3=ALr)
Digital input polarity (18-19)
Digital input configuration (18-19)
EAL; bAL; PAL; dor; dEF; ES; AUS;
Htr; FAn; HdF; onF
Digital input alarm delay (18-20)
Number of activation of pressure switch
Compress and fan status when open
door
Regulation restart with door open alarm
Differential for Energy Saving
[-30 to 30°C]
[-54 to 54°F]