1592040000 XR70T EN v1.1 2019.07.09 XR70T 20/40
dEF
EdF
Defrost mode
rtC
Pr2
rtC(0); in(1)
dEF
tdF
Defrost type: electric heating, hot gas
EL
Pr2
EL(0); in(1)
dEF
dFP
Probe selection for defrost control
P2
Pr2
nP(0); P1(1); P2(2); P3(3);
P4(4)
dEF
dtE
End defrost temperature
8.0
Pr2
°C
[-50.0°C to 50.0°C]
[-58.0°F to 122.0°F]
dEF
idF
Interval between two successive defrost
cycles
24
Pr2
ora
0 to 255 hours
dEF
MdF
Maximum length of defrost cycle
20
Pr2
min
0 to 255 min
dEF
dSd
Start defrost delay
0
Pr2
sec
0 to 255 sec
dEF
StC
Compressor stop before starting any
defrost
0
Pr2
sec
0 to 255 sec
dEF
dFd
Displaying during defrost
dEF
Pr2
rt(0); it(1); SEt(2); dEF(3);
Coo(4)
dEF
dAd
Temperature display delay after any
defrost cycle
0
Pr2
min
0 to 255 min
dEF
Fdt
Draining time
1
Pr2
min
0 to 255 min
dEF
Hon
Drain heater enabled after draining time
(par. Fdt)
2
Pr2
min
0 to 255 min
dEF
dPo
Defrost cycle enebled at stat-up
no
Pr2
n(0); Y(1)
dEF
od1
Automatic defrost (at the beginning of
any energy saving mode)
no
Pr2
n(0); Y(1)
FAn
FAP
Probe selection for evaporator fan
P2
Pr2
nP(0); P1(1); P2(2); P3(3);
P4(4)
FAn
FSt
Evaporator fan stop temperature
10.0
Pr2
°C
[-50.0°C to 50.0°C]
[-58.0°F to 122.0°F]
FAn
HYF
Evaporator fan regulator differential
2.0
Pr2
°C
[0.1°C to 25.0 °C]
[0.1°F to 45.0°F]
FAn
FnC
Evaporator fan operating mode
C_n
Pr2
C-n(0); O-n(1); C-Y(2); O-Y(3)
FAn
Fnd
Evaporator fan delay after defrost cycle
1
Pr2
min
0 to 255 min
FAn
FCt
Differential temperature for cyclic
activation of evaporator fans
(o=disabled)
0
Pr2
°C
[0°C to 50°C]
[0°F to 90°F]
FAn
FSU
Evaporator fan operating mode
Std
Pr2
Std(0); FoF(1); Fon(2)
FAn
Ft
Evaporator fan controlled during defrost
no
Pr2
n(0); Y(1)
FAn
Fon
Evaporator fan ON time in normal mode
(with compressor OFF)
5
Pr2
min
0 to 255 min
FAn
FoF
Evaporator fan OFF time in normal
mode (with compressor OFF)
10
Pr2
min
0 to 255 min
FAn
Fo1
Evaporator fan ON time in energy
saving mode (with compressor OFF)
5
Pr2
min
0 to 255 min
FAn
FF1
Evaporator fan OFF time in energy
saving mode (with compressor OFF)
10
Pr2
min
0 to 255 min
FAn
Fd1
Evaporator fan delay
0
Pr2
sec
0 to 255 sec
FAn
Fd2
Evaporator fan delay after closing door
0
Pr2
sec
0 to 255 sec
FAn
FAC
Probe selection for condenser fan
P3
Pr2
nP(0); P1(1); P2(2); P3(3);
P4(4)
FAn
St2
Set Point 2 regulation (for condenser
fan)
10.0
Pr2
°C
[-100.0°C to 150.0°C]
[-148.0°F to 302.0°F]
FAn
Hy2
Set Point 2 differential (for condenser
fan)
10.0
Pr2
°C
[0.1°C to 25.0°C]
[0.1°F to 45.0°F]
FAn
FCC
Condenser fan operating mode
C_n
Pr2
C-n(0); O-n(1); C-Y(2); O-Y(3)
FAn
Fd3
Condenser fan activation delay
0
Pr2
sec
0 to 255 sec
FAn
Fd4
Condenser fan deactivation delay
0
Pr2
sec
0 to 255 sec
AUS
ACH
Type of control for auxiliary regulator
CL
Pr2
CL(0); Ht(1)
AUS
SAA
Set point for auxiliary regulator
5.0
Pr2
°C
[-100.0°C to 150.0°C]
[-148.0°F to 302.0°F]