1592040000 XR70T EN v1.1 2019.07.09 XR70T 20/40
Defrost type: electric heating, hot gas
Probe selection for defrost control
nP(0); P1(1); P2(2); P3(3);
P4(4)
[-50.0°C to 50.0°C]
[-58.0°F to 122.0°F]
Interval between two successive defrost
cycles
Maximum length of defrost cycle
Compressor stop before starting any
defrost
Displaying during defrost
rt(0); it(1); SEt(2); dEF(3);
Coo(4)
Temperature display delay after any
defrost cycle
Drain heater enabled after draining time
(par. Fdt)
Defrost cycle enebled at stat-up
Automatic defrost (at the beginning of
any energy saving mode)
Probe selection for evaporator fan
nP(0); P1(1); P2(2); P3(3);
P4(4)
Evaporator fan stop temperature
[-50.0°C to 50.0°C]
[-58.0°F to 122.0°F]
Evaporator fan regulator differential
[0.1°C to 25.0 °C]
[0.1°F to 45.0°F]
Evaporator fan operating mode
C-n(0); O-n(1); C-Y(2); O-Y(3)
Evaporator fan delay after defrost cycle
Differential temperature for cyclic
activation of evaporator fans
(o=disabled)
[0°C to 50°C]
[0°F to 90°F]
Evaporator fan operating mode
Evaporator fan controlled during defrost
Evaporator fan ON time in normal mode
(with compressor OFF)
Evaporator fan OFF time in normal
mode (with compressor OFF)
Evaporator fan ON time in energy
saving mode (with compressor OFF)
Evaporator fan OFF time in energy
saving mode (with compressor OFF)
Evaporator fan delay after closing door
Probe selection for condenser fan
nP(0); P1(1); P2(2); P3(3);
P4(4)
Set Point 2 regulation (for condenser
fan)
[-100.0°C to 150.0°C]
[-148.0°F to 302.0°F]
Set Point 2 differential (for condenser
fan)
[0.1°C to 25.0°C]
[0.1°F to 45.0°F]
Condenser fan operating mode
C-n(0); O-n(1); C-Y(2); O-Y(3)
Condenser fan activation delay
Condenser fan deactivation delay
Type of control for auxiliary regulator
Set point for auxiliary regulator
[-100.0°C to 150.0°C]
[-148.0°F to 302.0°F]