Instruction Manual
D200138X012
3582, 582i, and 3583
January 2013
9
CSA
Intrinsically Safe, Explosion proof, Type n, Dust‐Ignition proof, DIV 2
No special conditions for safe use.
Refer to table 4 for additional information, figure 28 for CSA loop schematics, and figure 29 for a typical CSA/FM
approval nameplate.
Table 4. Hazardous Area Classifications for Fisher 582i Converter
(1)
—CSA (Canada)
Certification
Body
Certification Obtained Entity Rating Temperature Code Enclosure Rating
CSA
Intrinsically Safe
Ex ia IIC T4/T5/T6 per drawing GE28591
Ex ia Intrinsically Safe
Class I, II Division 1 GP A,B,C,D,E,F,G T4/T5/T6
per drawing GE28591
Vmax = 30 VDC
Imax = 150 mA
Pi = 1.25 W
Ci = 0 nF
Li = 0 mH
T4 (Tamb ≤ 71°C)
T5 (Tamb ≤ 62°C)
T6 (Tamb ≤ 47°C)
CSA Type 3 Encl.
Explosion Proof
Ex d IIC T6
Class I, Division I, GP A,B,C,D T6
- - - T6 (Tamb ≤ 71°C) CSA Type 3 Encl.
Type n
Ex nA IIC T6
- - - T6 (Tamb ≤ 71°C) CSA Type 3 Encl.
Class I, Division 2, GP A,B,C,D T6
Class II, Division 1 GP E,F,G T6
Class II Division 2 GP F,G T6
- - - T6 (Tamb ≤ 71°C) CSA Type 3 Encl.
1.These hazardous area classification also apply to 3582i positioners.
FM
Intrinsically Safe, Explosion proof, Type n, Non‐incendive, Dust‐Ignition proof
No special conditions for safe use.
Refer to table 5 for additional information, figure 30 for the FM loop schematic, and figure 29 for a typical CSA/FM
approval nameplate.
Table 5. Hazardous Area Classifications for Fisher 582i Converter
(1)
—FM (United States)
Certification
Body
Certification Obtained Entity Rating Temperature Code Enclosure Rating
FM
Intrinsically Safe
Class I Zone 0 AEx ia IIC T4/T5/T6
per drawing GE28590
Class I, II, III Division 1 GP A,B,C,D,E,F,G
T4/T5/T6 per drawing GE28590
Vmax = 30 VDC
Imax = 150 mA
Pi = 1.25 W
Ci = 0 nF
Li = 0 mH
T4 (Tamb ≤ 71°C)
T5 (Tamb ≤ 62°C)
T6 (Tamb ≤ 47°C)
NEMA 3, IP54
Explosion Proof
Class I Zone 1 AEx d IIC T6
Class I, Division I, GP A,B,C,D T6
- - - T6 (Tamb ≤ 71°C) NEMA 3, IP54
Type n
Class I Zone 2 AEx nA IIC T6
- - - T6 (Tamb ≤ 71°C) NEMA 3, IP54
Class I Division 2, GP A,B,C,D T6
Class II Division 1, GP E,F,G T6
Class II Division 2, GP F,G T6
- - - T6 (Tamb ≤ 71°C) NEMA 3, IP54
1.These hazardous area classification also apply to 3582i positioners.