Introduction
This installation guide provides instructions for installation,
startup and adjustment. To receive a copy of the
instruction manual, contact your local Sales Office or view
a copy at www.fisher.com. For further information refer to:
Type 92B Instruction Manual, D100703X012.
PED Categories
This product may be used as a safety accessory with
pressure equipment in the following Pressure Equipment
Directive categories. It may also be used outside of the
Pressure Equipment Directive using sound engineering
practice (SEP) per table below. For information on the
current PED revision see Bulletin: D103053X012.
PRODUCT SIZE CATEGORIES FLUID TYPE
DN 25 / NPS 1 SEP
1
DN 40, 50, 80, 100 / NPS 1-1/2, 2, 3, 4 II
Specifications
Available Configurations
Pilot-operated, globe-style pressure reducing
valve with post guiding and ow-to-close valve
plug action
Body Size and End Connection Style
See Table 1
Maximum Inlet Pressures and Temperatures
(1)
See Table 3
Maximum Outlet (Casing) Pressure
Cast Iron: 10.3 bar / 150 psig or body rating limit,
whichever is lower
Steel/Stainless steel: 20.7 bar / 300 psig or body
rating limit, whichever is lower
Proof Test Pressure
All Pressure Retaining Components have been
proof tested per Directive.
Outlet Pressure Ranges
(1)
See Table 2
Minimum Di󰀨erential Pressure Required for
Full Stroke
(1)
1.4 bar / 20 psig with stainless steel
spring; 0.69 bar / 10 psig with Inconel
®
spring
Installation
!
WARNING
Only qualied personnel should install
or service a regulator. Regulators
should be installed, operated and
maintained in accordance with
international and applicable codes
and regulations and Emerson Process
Management Regulator Technologies,
Inc. instructions.
If the regulator vents uid or a leak
develops in the system, it indicates that
service is required. Failure to take the
regulator out of service immediately may
create a hazardous condition.
Personal injury, equipment damage or
leakage due to escaping uid or bursting
of pressure-containing parts may result
if this regulator is overpressured or
is installed where service conditions
could exceed the limits given in the
Specications section, or where
conditions exceed any ratings of the
adjacent piping or piping connections.
To avoid such injury or damage, provide
pressure-relieving or pressure-limiting
devices (as required by the appropriate
code, regulation or standard) to prevent
service conditions from exceeding limits.
Additionally, physical damage to the
regulator could result in personal injury
and property damage due to escaping
uid. To avoid such injury and damage,
install the regulator in a safe location.
Clean out all pipelines before installation of the
regulator and check to be sure the regulator has not
been damaged or has collected foreign material during
shipping. For NPT bodies, apply pipe compound to the
external pipe threads. For anged bodies, use suitable
line gaskets and approved piping and bolting practices.
Install the regulator in any position desired, unless
otherwise specied, but be sure ow through the body
is in the direction indicated by the arrow on the body.
Inconel
®
is a trademark owned by Special Metals Corporation.
1. The pressure/temperature limits in this installation guide or any applicable standard limitation should not be exceeded.
Type 92B
Installation Guide
D100703X014
English – October 2014

Other manuals for Emerson Fisher 92B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher 92B and is the answer not in the manual?

Emerson Fisher 92B Specifications

General IconGeneral
BrandEmerson
ModelFisher 92B
CategoryControl Unit
LanguageEnglish

Related product manuals